Proper Electrode Location; Flame Current Measurement - ALLIANCE CA050L Installation Operation & Maintenance

050 series 075 series 50 pound (22.7 kilogram) capacity 75 pound (34 kilogram) capacity
Hide thumbs Also See for CA050L:
Table of Contents

Advertisement

Proper Electrode Location

Proper location of the electrode assembly is important
for optimal system performance. The electrode
assembly should be located so that the tips are inside
the flame envelope and about 1/2 inch (1.2 cm) above
the base of the flame. Refer to Figure 53.
BURNER
BURNER
YES
Figure 53
70457901ENR7
BURNER
NO
NO
TMB 2317K
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT

Flame Current Measurement

Flame current is the current that passes through the
flame from sensor to ground. To measure flame
current, connect a True RMS or analog DC micro-
ammeter to the FC+ and the FC- terminals. The
reading should be 1.0 micro-amps DC or higher. If the
meter reads negative or below "0" on the scale, the
meter leads are reversed. Re-connect leads with proper
polarity.
Alternately, a Digital Voltmeter may be used to
measure the DC voltage between the FC+ and FC-
terminals. Each micro-amp of flame current produces
1.0 VDC, so a reading of 2.6 VDC would equate to 2.6
micro-amps.
A good burner ground that matches the control ground
is critical for reliable flame sensing.