4 FUNCTIONS

4.2.5 Parameter setting with GX Developer

Network parameter
Automatic refresh parameter
GX Developer
4 - 22
Using GX Developer makes the setting of the network parameters and automatic
refresh parameters easier.
The data link is automatically started if GX Developer is used to set the parameters.
Using GX Developer to set the parameters has the following advantages:
• It is not necessary to write a program for setting the parameters.
• It is possible to perform automatic refresh in the system.
POINT
In case a system includes both a module for which the network parameters are set
by GX Developer and a module for which the network parameters are set by the
dedicated instruction (RLPASET), the module for which the network parameters
are set by the RLPASET instruction should not be included in the "No. of boards in
module" setting of GX Developer.
Write to PLC
[Setting method]
For more details on the setting, see Sections 6.3 to 6.6.
Master station
Local station
Data link start
MELSEC-Q
Remote I/O station Remote device station
4 - 22