10 COMMUNICATION BETWEEN THE MASTER STATION AND REMOTE
DEVICE STATIONS
PLC CPU
For write
For read
10 - 14
[Remote registers (RWw and RWr)]
W100
W101
W102
W103
W104
W105
W106
W107
W108
W109
W10A
W10B
W000
W001
W002
W003
W004
W005
W006
W007
W008
W009
W00A
W00B
Remote device station (station number 1)
AJ65VBTCU-68ADV
RWw0 (A/D conversion enable/prohibit specification)
RWw1 (CH.1 to CH.4 input range setting)
RWw2 (CH.5 to CH.8 input range setting)
RWw3 (Average processing specification)
RWw4 (CH.1 average time, number of times setting)
RWw5 (CH.2 average time, number of times setting)
RWw6 (CH.3 average time, number of times setting)
RWw7 (CH.4 average time, number of times setting)
RWw8 (CH.5 average time, number of times setting)
RWw9 (CH.6 average time, number of times setting)
RWwA (CH.7 average time, number of times setting)
RWwB (CH.8 average time, number of times setting)
RWr0 (CH.1 digital output value)
RWr1 (CH.2 digital output value)
RWr2 (CH.3 digital output value)
RWr3 (CH.4 digital output value)
RWr4 (CH.5 digital output value)
RWr5 (CH.6 digital output value)
RWr6 (CH.7 digital output value)
RWr7 (CH.8 digital output value)
RWr8 (Error code)
RWr9 (Reserved)
RWrA (Reserved)
RWrB (Reserved)
MELSEC-Q