[DESIGN PRECAUTION]
Do not write data into the "system area" of the buffer memory of intelligent function modules.
Also, do not output the "prohibited to use" signal as the output signal to an intelligent function
module from the PLC CPU.
Writing data into the "system area" or outputting a signal for "prohibited to use" may cause
system malfunction in the PLC.
To specify the automatic refresh parameter, specify "Y" for the remote output RY refresh device.
If a value other than "Y" (for example, M or L) is specified, the status of the device will remain as
it was prior to the STOP operation when the CPU is stopped.
See Section 4.4.10 for how to stop the data link.
If wire breakage occurs in the CC-Link dedicated cable, the line may become instable, resulting in
a data link communication error at multiple stations. Configure an interlock circuit in a sequence
program to operate the system toward the safety side if a data link communication error occurs at
multiple stations. Failure to do so may result in an accident due to false output or malfunction.
[DESIGN PRECAUTION]
Do not bunch the control wires or communication cables with the main circuit or power wires, or
install them close to each other.
They should be installed 100mm(3.9inch) or more from each other.
Not doing so could result in noise that may cause malfunction.
[INSTALLATION PRECAUTIONS]
Use the PLC in an environment that meets the general specifications contained in the CPU
user's manual to use.
Using this PLC in an environment outside the range of the general specifications may cause
electric shock, fire, malfunction, and damage to or deterioration of the product.
While pressing the installation lever located at the bottom of module, insert the module fixing tab
into the fixing hole in the base unit until it stops. Then, securely mount the module with the fixing
hole as a supporting point.
Improper installation may result in malfunction, breakdown or dropping out of the module.
Securely fix the module with screws if it is subject to vibration during use.
Tighten the screws within the range of specified torque.
If the screws are loose, it may cause fallout, short circuits, or malfunction.
If the screws are tightened too much, it may cause damage to the screw and/or the module,
resulting in fallout, short circuits or malfunction.
Switch all phases of the external power supply off when mounting or removing the module.
Not doing so may cause damage to the module.
Do not directly touch the conductive area or electronic components of the module.
Doing so may cause malfunction or failure in the module.