6 PARAMETER SETTINGS
6.6 Example of Parameter Settings with GX Developer (Remote I/O net mode)
(X/Y00 to 1F)
6.6.1 Master station network parameter settings
6 - 43
This section explains the parameter settings using the GX Developer. For more details
on the GX Developer operation, refer to the GX Developer Operating Manual.
The explanations in this section are based on the following example of the system
configuration.
Station
number 1
Master
station
Remote
I/O station
(occupies
1 station)
(1) The following describes an example of the parameter settings. See (2) for actual
settings.
(2) Set the network parameters using the following procedure.
(a) Set the "No. of boards in module" for which the network parameters are to be
set.
Default value : None
Setting range: 0 to 4 (Boards)
Example) Set 1 (Board).
(b) Set the "Start I/O No." for the master station.
Default value : None
Setting range: 0000 to 0FE0
Example) Set 0000.
Station
Station
number 2
number 3
Remote
Remote
I/O station
I/O station
(occupies
(occupies
1 station)
1 station)
Modules for the parameter setting with the RLPASET instruction
should not be included in the setting for "No. of boards in
module".
Station
Station
number 4
number 5
Remote
Remote
I/O station
I/O station
(occupies
(occupies
1 station)
1 station)
MELSEC-Q