Mitsubishi MELSEC Q Series User Manual page 163

Cc-link system master/local module
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

5 DATA LINK PROCESSING TIME
5 - 42
(2) Remote net additional mode
[Expression]
KM1 + KM2
[{(RX + RX2) + (RY + RY2) + SB + (RWw + RWw2)
+ RWr2)
16 + (SW
αE = KM3
[(RX + RX2) + (RY + RY2) + SB + (RWw + RWw2)
RWr2)
16 + (SW
RX
: Points of the remote input (RX) refreshed by the master/local station
RX2
: Points of the ver. 2 remote input (RX) refreshed by the master/local
station
RY
: Points of the remote output (RY) refreshed by the master/local station
RY2
: Points of the ver. 2 remote output (RY) refreshed by the master/local
station
RWw : Points of the remote register (RWw) refreshed by the master/local
station
RWw2 : Points of the ver. 2 remote register (RWw) refreshed by the master/local
station
RWr : Points of the remote register (RWr) refreshed by the master/local station
RWr2 : Points of the ver. 2 remote register (RWr) refreshed by the master/local
station
SB
: Points of the link special relay (SB) refreshed by the master/local station
SW
: Points of the link special register (SW) refreshed by the master/local
station
αE
: File register (R, ZR) transfer time on memory card (only when file
register is used)
KM1 : Constant
1) Master station
CPU type
Q02CPU
Q02HCPU, Q06HCPU, Q12HCPU, Q25HCPU
2) Local station
CPU type
Q02CPU
Q02HCPU, Q06HCPU, Q12HCPU, Q25HCPU
16)} / 16] + αE [ms]
16)} / 16]
MELSEC-Q
16 + (RWr
16 + (RWr +
Constant
KM1
0.57
0.22
Constant
KM1
0.76
0.32
5 - 42

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Qj61bt11n