13 TROUBLESHOOTING
Description of problem
Unable to receive remote input (RX) of a remote
device station.
Unable to turn on/off remote output (RY) of a remote
device station.
13 - 3
Check item
Is data read from the correct address of remote
input RX (buffer memory)?
Is the correct master station parameter information
area being used (CPU built-in parameters, default
parameters)?
Is the corresponding remote device station number
recognized by the master station?
Is the corresponding station set as a reserved
station?
Are there any overlap station numbers?
Do the settings match?
Are the refresh set with the automatic refresh
parameters and the refresh executed with the
FROM/TO instructions performed simultaneously?
Is the remote device station initialization procedure
registration being executed?
Is the corresponding remote device station
performing data link?
Is data read from the correct address of remote
output RY (buffer memory)?
Is the correct master station parameter information
area being used (CPU built-in parameters, default
parameters)?
Is the corresponding remote device station number
recognized by the master station?
Is the corresponding station set as a reserved
station?
Are there any overlap station numbers?
Do the settings match?
MELSEC-Q
Check procedure
• Check the sequence program.
• Check the automatic refresh parameter setting.
Check parameter information (SW0067).
• Check the parameters.
• Check the total number of stations (SW0070).
• Check the max. communication station number
(SW0071).
• Check the number of connected modules
(SW0072).
• Check the parameters.
• Check the reserved station specified status
(SW0074 to SW0077).
• Check the station number setting.
• Check the loading status (SW0069).
• Check the station number overlap status
(SW0098 to SW009B).
• Check the loading status (SW0069).
• Check the station number overlap status
(SW0098 to SW009B).
• Check the loading/parameter consistency status
(SW009C to SW009F).
• Check the sequence program.
• Check the automatic refresh parameter settings.
Check if the remote device station initialization
procedure registration instruction (SB000D) is on.
• Check the LED display on the corresponding
remote device station.
• Check the other station data link status of the
master station. (SW0080 to SW0083)
• Check the sequence program.
• Check the automatic refresh parameter setting.
Check parameter information (SW0067).
• Check the parameters.
• Check the total number of stations (SW0070).
• Check the max. communication station number
(SW0071).
• Check the number of connected modules
(SW0072).
• Check the parameters.
• Check the reserved station specified status
(SW0074 to SW0077).
• Check the station number setting.
• Check the loading status (SW0069).
• Check the station number overlap status
(SW0098 to SW009B).
• Check the loading status (SW0069).
• Check the station number overlap status
(SW0098 to SW009B).
• Check the loading/parameter consistency status
(SW009C to SW009F).
13 - 3