10 COMMUNICATION BETWEEN THE MASTER STATION AND REMOTE
DEVICE STATIONS
10 - 24

(2) Setting the automatic refresh parameters of the master station

(a) Setting the automatic refresh parameters
Set the automatic refresh parameters according to the procedure below.
1) Set the refresh device for remote input (RX) to X1000.
2) Set the refresh device for remote output (RY) to Y1000.
3) Set the refresh device for remote register (RWr) to W0.
4) Set the refresh device for remote register (RWw) to W1000.
5) Set the refresh device for special relay (SB) to SB0.
6)
Set the refresh device for special register (SW) to SW0.
POINT
When setting X, Y, B, W, SB and SW as refresh devices, make setting so that they
do not overlap with the device numbers used on the other networks, etc.
(b) Setting example
A setting example is shown below.
MELSEC-Q
10 - 24