Editing the Liebert IntelliSlot Unity Card Configuration
5.5.1
Protocols—BACnet Folder
BACnet Settings
Managed Device Write Access
Enable or Disable the BACnet server to write to the managed device.
BACnet Interface
BACnet server interface: BACnet IP or BACnet MSTP.
Device Object Instance Number
The instance number (0-4194302) of the BACnet server's device object.
Device Object Name
The name of the BACnet server's device object.
APDU Timeout
The timeout in milliseconds between APDU retries (1-65535).
APDU Retries
The number of times to retransmit an APDU after the initial attempt (0-8).
®