3.1.2.2

Configure BACnet MSTP Protocol

NOTE
Contact your system administrator if you are uncertain about the settings.
1. Select Communications tab > Protocols > BACnet MSTP.
2. Click Edit and enter a user name and password if required.
3. Set the BACnet MSTP Node ID.
• The Node ID defaults to 1, but must have a value from 1 to 255 that is unique among devices
connected through the RS-485 interface.
4. Set the BACnet MSTP Data Rate.
5. Set the BACnet MSTP Max Master Address.
6. Set the BACnet MSTP Max Info Frames.
For descriptions of the settings, see 5.5.1.2 - BACnet MSTP Folder.
7. Click Save to confirm the changes or Cancel to discard them.
8. Restart the card to activate the changes.
a. Select Communications tab > Support.
b. Enable the commands.
c. Click Restart.