B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 50 of 71)
ADDR
REGISTER NAME
A378
...Repeated for Digital Counter 4
A3A0
...Repeated for Digital Counter 5
A3C8
...Repeated for Digital Counter 6
A3F0
...Repeated for Digital Counter 7
A418
...Repeated for Digital Counter 8
B
Flexcurves C and D (Read/Write Setting)
A600
FlexCurve C (120 items)
A680
FlexCurve D (120 items)
Non Volatile Latches (Read/Write Setting) (16 modules)
A700
Non-Volatile Latch 1 Function
A701
Non-Volatile Latch 1 Type
A702
Non-Volatile Latch 1 Set
A704
Non-Volatile Latch 1 Reset
A706
Non-Volatile Latch 1 Target
A707
Non-Volatile Latch 1 Events
A708
Reserved (4 items)
A70C
...Repeated for Non-Volatile Latch 2
A718
...Repeated for Non-Volatile Latch 3
A724
...Repeated for Non-Volatile Latch 4
A730
...Repeated for Non-Volatile Latch 5
A73C
...Repeated for Non-Volatile Latch 6
A748
...Repeated for Non-Volatile Latch 7
A754
...Repeated for Non-Volatile Latch 8
A760
...Repeated for Non-Volatile Latch 9
A76C
...Repeated for Non-Volatile Latch 10
A778
...Repeated for Non-Volatile Latch 11
A784
...Repeated for Non-Volatile Latch 12
A790
...Repeated for Non-Volatile Latch 13
A79C
...Repeated for Non-Volatile Latch 14
A7A8
...Repeated for Non-Volatile Latch 15
A7B4
...Repeated for Non-Volatile Latch 16
Pilot POTT (1P) (Read/Write Setting)
A800
POTT 1P Scheme Function
A801
POTT 1P Permissive Echo
A802
POTT 1P Rx Pickup Delay
A803
POTT 1P Trans Block Pickup Delay
A804
POTT 1P Trans Block Reset Delay
A805
POTT 1P Echo Duration
A806
POTT 1P Echo Lockout
A807
POTT 1P Line End Open Pickup Delay
A808
POTT 1P Seal In Delay
A809
POTT 1P Ground Directional Overcurrent Forward
A80B
POTT 1P Number of Communication Bits
A80C
POTT 1P Rx1
A80E
POTT 1P Rx2
A810
POTT 1P Rx3
A812
POTT 1P Rx4
A814
POTT 1P Target
A815
POTT 1P Event
A816
POTT 1P Echo Condition
A818
POTT 1P Scheme Block
A81A
Reserved (22 items)
B-58
RANGE
0 to 65535
0 to 65535
0 to 1
0 to 1
0 to 4294967295
0 to 4294967295
0 to 2
0 to 1
---
0 to 1
0 to 2
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 4294967295
0 to 2
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 2
0 to 1
0 to 4294967295
0 to 4294967295
0 to 1
L90 Line Current Differential System
APPENDIX B
UNITS
STEP
FORMAT
ms
1
F011
ms
1
F011
---
1
F102
---
1
F519
---
1
F300
---
1
F300
---
1
F109
---
1
F102
---
---
F001
---
1
F102
---
1
F199
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
---
1
F300
---
1
F198
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F109
---
1
F102
---
1
F300
---
1
F300
---
1
F001
DEFAULT
0
0
0 (Disabled)
0 (Reset
Dominant)
0
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (Disabled)
0
20
90
100
250
50
0
0
0 (1)
0
0
0
0
0 (Self-reset)
0 (Disabled)
0
0
0
GE Multilin