5.2 PRODUCT SETUP
c) TRIP AND ALARM LEDS
PATH: SETTINGS
PRODUCT SETUP
 TRIP & ALARM LEDS
The trip and alarm LEDs are in the first LED column (enhanced faceplate) and on LED panel 1 (standard faceplate). Each
indicator can be programmed to become illuminated when the selected FlexLogic operand is in the logic 1 state.
d) USER-PROGRAMMABLE LED 1(48)
PATH: SETTINGS
PRODUCT SETUP
 USER-PROGRAMMABLE
 LED 1
There are 48 amber LEDs across the relay faceplate LED panels. Each of these indicators can be programmed to illumi-
nate when the selected FlexLogic operand is in the logic 1 state.
For the standard faceplate, the LEDs are located as follows.
LED Panel 2: user-programmable LEDs 1 through 24
5
LED Panel 3: user programmable LEDs 25 through 48
For the enhanced faceplate, the LEDs are located as follows.
LED column 2: user-programmable LEDs 1 through 12
LED column 3: user-programmable LEDs 13 through 24
LED column 4: user-programmable LEDs 25 through 36
LED column 5: user-programmable LEDs 37 through 48
Refer to the LED indicators section in chapter 4 for additional information on the location of these indexed LEDs.
The user-programmable LED settings select the FlexLogic operands that control the LEDs. If the
Reset" (the default setting), the LED illumination will track the state of the selected LED operand. If the
"Latched", the LED, once lit, remains so until reset by the faceplate RESET button, from a remote device via a communica-
tions channel, or from any programmed operand, even if the LED operand state de-asserts.
Table 5–4: RECOMMENDED SETTINGS FOR USER-PROGRAMMABLE LEDS
SETTING
LED 1 operand
LED 2 operand
LED 3 operand
LED 4 operand
LED 5 operand
LED 6 operand
LED 7 operand
LED 8 operand
LED 9 operand
LED 10 operand
LED 11 operand
LED 12 operand
5-60

USER-PROGRAMMABLE LEDS
TRIP LED INPUT:
Off
ALARM LED INPUT:
MESSAGE
Off

USER-PROGRAMMABLE LEDS
LED 1 OPERAND:
Off
LED 1 TYPE:
MESSAGE
Self-Reset
PARAMETER
SETTING GROUP ACT 1
SETTING GROUP ACT 2
SETTING GROUP ACT 3
SETTING GROUP ACT 4
SETTING GROUP ACT 5
SETTING GROUP ACT 6
Off
Off
BREAKER 1 OPEN
BREAKER 1 CLOSED
BREAKER 1 TROUBLE
Off
L90 Line Current Differential System

TRIP & ALARM LEDS
Range: FlexLogic operand
Range: FlexLogic operand

USER-PROGRAMMABLE LED 1(48)
Range: FlexLogic operand
Range: Self-Reset, Latched
SETTING
PARAMETER
LED 13 operand
Off
LED 14 operand
BREAKER 2 OPEN
LED 15 operand
BREAKER 2 CLOSED
LED 16 operand
BREAKER 2 TROUBLE
LED 17 operand
SYNC 1 SYNC OP
LED 18 operand
SYNC 2 SYNC OP
LED 19 operand
Off
LED 20 operand
Off
LED 21 operand
AR ENABLED
LED 22 operand
AR DISABLED
LED 23 operand
AR RIP
LED 24 operand
AR LO
5 SETTINGS
setting is "Self-
LED 1 TYPE
setting is
LED 1 TYPE
GE Multilin