GE L90 Instruction Manual page 246

Ur series line current differential system
Hide thumbs Also See for L90:
Table of Contents

Advertisement

5.4 SYSTEM SETUP

PATH: SETTINGS
SYSTEM SETUP
URATION
 37.118 AGGR 1
 CONFIGURATION

PATH: SETTINGS
SYSTEM SETUP
RATION
 90-5 AGGR 1
 CONFIGURATION
PMU AGGREGATOR1 PROTOCOL: This setting selects if C37.118 or the new IEC61850 standard will be used.
PMU AGGREGATOR1 IDCODE: Numeric identifier of the Aggregator / PDC function. In an IEEE C37.118 output
stream, this identifies the ID of the aggregator - which is only used if there is more than 1 PMU mapped into an aggre-
gator.
5
AGGREGATOR1: PHYSICAL PORT: This setting determines which physical ports through which the synchrophasor
traffic will be transmitted. The range is 1, 2, 3.
PMU AGGREGATOR1 PMU1 to PMU4: If set to "Yes" aggregator 1 includes the PMU1 data set in the reporting data
stream. AGGREGATOR1 will not include PMU1 data set in the report if set to "No".
C37.118 AGGREGATOR 1 CONFIGURATION
PMU AGGREGATOR1: TCP PORT: This setting selects the TCP port number that will be used by this aggregator for
network reporting. When using more than one aggregator, the default value of the port must be properly changed to
avoid port number collisions.
PMU AGGREGATOR1 UDP PORT: This setting selects the UDP port number that will be used by this aggregator for
network reporting. When using more than one aggregator, the default value of the port must be properly changed to
avoid port number collisions.
PMU AGGREGATOR1 PDC CONTROL: The synchrophasor standard allows for user-defined controls originating at
the PDC, to be executed on the PMU. The control is accomplished via an extended command frame. The relay
decodes the first word of the extended field, EXTFRAME, to drive 16 dedicated FlexLogic operands. Each aggregator
supports 16 FlexLogic operands as shown in table 2. The operands are asserted for 5 seconds following reception of
the command frame. If the new command frame arrives within the 5 second period, the FlexLogic operands are
updated, and the 5 second timer is re-started. This setting enables or disables the control. When enabled, all 16 oper-
ands for each aggregator are active; when disabled all 16 operands for each aggregator remain reset.
Table 5–7: FLEXLOGIC OPERANDS SUPPORTED BY AGGREGATOR
OPERAND TYPE
ELEMENT:
Synchrophasor, phasor data,
concentrator
as above
as above
as above
5
-
1
1
6

PHASOR MEASUREMENT UNIT
PMU AGGREGATOR 1
TCP PORT: 4712
PMU AGGREGATOR 1
MESSAGE
UDP PORT: 4713
PMU AGGREGATOR 1
MESSAGE
PDC CONTROL: Disabled

PHASOR MEASUREMENT UNIT
PMU AGGREGATOR 1
NAME:
PMU AGGREGATOR 1:
MESSAGE
UDP PORT: 102
PMU AGGREGATOR 1:
MESSAGE
NUMBER OF ASDUs: 1
OPERAND SYNTAX
AGTR1 PDC CNTRL 1
AGTR1 PDC CNTRL 2
AGTR1 PDC CNTRL 3
AGTR1 PDC CNTRL 16
L90 Line Current Differential System

PMU AGGREGATOR 1
Range: 1 to 65534
Default: 4712
Range: 1 to 65534
Default: 4713
Range: Disabled, Enabled
Default: Disabled

PMU AGGREGATOR 1
Range: 56 character ASCII text
Default: Blank
Range: 1 to 65534 in steps of 1
Default: 102
Range: 1 to 4
Default: 1
OPERAND DESCRIPTION
Phasor data concentrator asserts control bit 1, as
received via the network.
Phasor data concentrator asserts control bit 2 as
received via the network.
Phasor data concentrator asserts control bit 3 as
received via the network.
Phasor data concentrator asserts control bit 16, as
received via the network.
5 SETTINGS

37.118 AGGR 1 CONFIG-

90-5 AGGR 1 CONFIGU-
GE Multilin