5.7 CONTROL ELEMENTS
f) CT FAILURE DETECTOR

PATH: SETTINGS
CONTROL ELEMENTS
 CT FAILURE
 DETECTOR
5
The CT failure function is designed to detect problems with system current transformers used to supply current to the relay.
This logic detects the presence of a zero-sequence current at the supervised source of current without a simultaneous
zero-sequence current at another source, zero-sequence voltage, or some protection element condition.
The CT failure logic (see below) is based on the presence of the zero-sequence current in the supervised CT source and
the absence of one of three or all of the three following conditions.
1.
Zero-sequence current at different source current (may be different set of CTs or different CT core of the same CT).
2.
Zero-sequence voltage at the assigned source.
3.
Appropriate protection element or remote signal.
The CT failure settings are described below.
CT FAIL FUNCTION: This setting enables or disables operation of the CT failure element.
CT FAIL BLOCK: This setting selects a FlexLogic™ operand to block operation of the element during some condition
(for example, an open pole in process of the single pole tripping-reclosing) when CT fail should be blocked. Local sig-
nals or remote signals representing operation of some remote current protection elements via communication chan-
nels can also be chosen.
CT FAIL 3I0 INPUT 1: This setting selects the current source for input 1. The most critical protection element should
also be assigned to the same source.
CT FAIL 3I0 INPUT 1 PICKUP: This setting selects the 3I_0 pickup value for input 1 (the main supervised CT source).
CT FAIL 3I0 INPUT 2: This setting selects the current source for input 2. Input 2 should use a different set of CTs or a
different CT core of the same CT. If 3I_0 does not exist at source 2, then a CT failure is declared.
CT FAIL 3I0 INPUT 2 PICKUP: This setting selects the 3I_0 pickup value for input 2 (different CT input) of the relay.
CT FAIL 3V0 INPUT: This setting selects the voltage source.
5-272

MONITORING ELEMENTS
CT FAIL FUNCTION:
Disabled
CT FAIL BLOCK:
MESSAGE
Off
CT FAIL 3I0 INPUT 1:
MESSAGE
SRC 1
CT FAIL 3I0 INPUT 1
MESSAGE
PKP: 0.20 pu
CT FAIL 3I0 INPUT 2:
MESSAGE
SRC 2
CT FAIL 3I0 INPUT 2
MESSAGE
PKP: 0.20 pu
CT FAIL 3V0 INPUT:
MESSAGE
SRC 1
CT FAIL 3V0 INPUT
MESSAGE
PKP: 0.20 pu
CT FAIL PICKUP
MESSAGE
DELAY: 1.000 s
CT FAIL TARGET:
MESSAGE
Self-reset
CT FAIL EVENTS:
MESSAGE
Disabled
L90 Line Current Differential System

CT FAILURE DETECTOR
Range: Disabled, Enabled
Range: FlexLogic™ operand
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 0.00 to 2.00 pu in steps of 0.01
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 0.00 to 2.00 pu in steps of 0.01
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 0.00 to 2.00 pu in steps of 0.01
Range: 0.000 to 65.535 s in steps of 0.001
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
5 SETTINGS