GE L90 Instruction Manual page 679

Ur series line current differential system
Hide thumbs Also See for L90:
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 41 of 71)
ADDR
REGISTER NAME
77B3
Broken Conductor 1 Events
77B4
Reserved (2 items)
77B6
...Repeated for Broken Conductor 2
Ohm Inputs (Read/Write Setting) (2 modules)
77F8
Ohm Inputs 1 Function
77F9
Ohm Inputs 1 ID
77FF
Ohm Inputs 1 Reserved (9 items)
7808
...Repeated for Ohm Inputs 2
Phasor Measurement Unit Recorder Config Counter Command (Read/Write Command) (4 modules)
781A
PMU 1 Recorder Clear Config Counter
Phasor Measurement Unit Power Trigger (Read/Write Setting) (4 modules)
7820
PMU 1 Power Trigger Function
7821
PMU 1 Power Trigger Active
7822
PMU 1 Power Trigger Reactive
7823
PMU 1 Power Trigger Apparent
7824
PMU 1 Power Trigger Pickup Time
7825
PMU 1 Power Trigger Dropout Time
7826
PMU 1 Power Trigger Block (3 items)
782C
PMU 1 Power Trigger Target
782D
PMU 1 Power Trigger Events
Phasor Measurement Unit Voltage Trigger (Read/Write Setting) (4 modules)
7858
PMU 1 Voltage Trigger Function
7859
PMU 1 Voltage Trigger Low Voltage
785A
PMU 1 Voltage Trigger High Voltage
785B
PMU 1 Voltage Trigger Pickup Time
785C
PMU 1 Voltage Trigger Dropout Time
785D
PMU 1 Voltage Trigger Block (3 items)
7863
PMU 1 Voltage Trigger Target
7864
PMU 1 Voltage Trigger Events
Phasor Measurement Unit One-shot Command (Read/Write Setting)
78BC
PMU One-shot Function
78BD
PMU One-shot Sequence Number
788E
PMU One-shot Time
Phasor Measurement Unit Test Values (Read/Write Setting)
7890
PMU 1 Test Function
7891
PMU 1 Phase A Voltage Test Magnitude
7893
PMU 1 Phase A Voltage Test Angle
7894
PMU 1 Phase B Voltage Test Magnitude
7896
PMU 1 Phase B Voltage Test Angle
7897
PMU 1 Phase C Voltage Test Magnitude
7899
PMU 1 Phase C Voltage Test Angle
789A
PMU 1 Auxiliary Voltage Test Magnitude
789C
PMU 1 Auxiliary Voltage Test Angle
789D
PMU 1 Phase A Current Test Magnitude
789F
PMU 1 Phase A Current Test Angle
78A0
PMU 1 Phase B Current Test Magnitude
78A2
PMU 1 Phase B Current Test Angle
78A3
PMU 1 Phase C Current Test Magnitude
78A5
PMU 1 Phase C Current Test Angle
78A6
PMU 1 Ground Current Test Magnitude
78A8
PMU 1 Ground Current Test Angle
78A9
PMU 1 Test Frequency
78AB
PMU 1 Test df/dt
GE Multilin
RANGE
0 to 1
---
0 to 1
---
0 to 65535
0 to 1
0 to 1
0.25 to 3
0.25 to 3
0.25 to 3
0 to 600
0 to 600
0 to 4294967295
0 to 2
0 to 1
0 to 1
0.25 to 1.25
0.75 to 1.75
0 to 600
0 to 600
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 99
0 to 235959
0 to 1
0 to 700
-180 to 180
0 to 700
-180 to 180
0 to 700
-180 to 180
0 to 700
-180 to 180
0 to 9.999
-180 to 180
0 to 9.999
-180 to 180
0 to 9.999
-180 to 180
0 to 9.999
-180 to 180
20 to 70
-10 to 10
L90 Line Current Differential System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F102
---
---
F001
---
1
F102
---
---
F205
---
1
F001
---
1
F126
---
1
F102
pu
0.001
F001
pu
0.001
F001
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F102
pu
0.001
F001
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F102
---
1
F001
---
1
F050
---
1
F102
kV
0.01
F003
°
0.05
F002
kV
0.01
F003
°
0.05
F002
kV
0.01
F003
°
0.05
F002
kV
0.01
F003
°
0.05
F002
kA
0.001
F004
°
0.05
F002
kA
0.001
F004
°
0.05
F002
kA
0.001
F003
°
0.05
F002
kA
0.001
F004
°
0.05
F002
Hz
0.001
F003
Hz/s
0.01
F002
DEFAULT
0 (Disabled)
0
0 (Disabled)
B
"Ohm Ip 1 "
0
0 (No)
0 (Disabled)
1250
1250
1250
10
100
0
0 (Self-reset)
0 (Disabled)
0 (Disabled)
800
1200
10
100
0
0 (Self-reset)
0 (Disabled)
0 (Disabled)
1
0
0 (Disabled)
50000
0
50000
-12000
50000
120
50000
0
1000
-1000
1000
-13000
1000
11000
0
0
60000
0
B-49

Advertisement

Table of Contents
loading

Table of Contents