4 USER INTERFACE
To change SPM setpoints, the user must enter the PROGRAMMING MODE. This can be accomplished with
the motor either off or in running mode. Use the following procedure to enter the PROGRAMMING MODE:
1. With the display indicating the following, press the GE key (items in bold italics indicate that they should be
blinking on the screen):
Collr-Ring Motor
SPM READY
2. The display should now indicate that the unit is in STAT MODE. Press the GE key.
STAT MODE
SCROLL for menus
3. Press the GE key. The display should now indicate that the unit is in PROGRAMMING MODE:
PROGRAMMING MODE
SCROLL PASSWORD
4. Use the
/
PASSWORD: 0000
ENTER to verify
5. The display should now indicate the CONFIGURATIONS menu or the CALIBRATION menu (depending
upon which scroll key was pressed). Use the
SETPOINTS?
ENTER for menus
6. Press the
key to enter the setpoints menu. Once in the SETPOINTS menu, use the
move through the different setpoints.
7. To change a setpoint, press the
PF TRIP: –0.80
SELECT to modify
8. Once the setpoint has been selected, the value of the setpoint should blink. Use the
change the value of the setpoint and then press the
setpoint once it has been selected, pressing the GE key deselects the setpoint.
PF TRIP: –0.80
SCROLL to change
9. Additional setpoints can be changed using the above procedure. When all setpoint changes have been
accomplished, press the GE key. This will return the display to the SETPOINTS main menu. Press the GE
key again and the display will ask to verify that changes should be save. Press
otherwise press the GE key if you do not want to save the changes.
SAVE CHANGES?
ENTER to save ...
10. Upon pressing
the display returns to the PROGRAMMING MODE menu. Press the GE key once to go into TEST MODE
and a second time to return to the SPM READY display.
GE Multilin
Courtesy of store.ips.us
keys to change the password and then press the
key as prompted:
(to save the setpoint changes) or the GE key (not wanting to save setpoint changes),
SPM Synchronous Motor Protection and Control

4.2.2 CHANGING SETPOINTS

key to enter the password.
/
keys to select the SETPOINTS menu.
key to continue. If you choose not to change this
4.2 KEYPAD INTERFACE
/
keys to
/
keys to
to save the setpoints,
4-
4
11

Advertisement

Table of Contents
loading

This manual is also suitable for:

1601-0072-a9

Table of Contents