Name
MStart.JamStartBlock
MStart.UnbalStartBlock
MStart.Blo-Generic1
MStart.Blo-Generic2
MStart.Blo-Generic3
MStart.Blo-Generic4
MStart.Blo-Generic5
MStart.I_Transit
MStart.T_Transit
MStart.MotorStopBlo
MStart.RFD_IA_Normal
MStart.RFD_IA_Reverse
MStart.VUnbalStartBlock
MStart.UnderVStartBlock
MStart.OverVStartBlock
MStart.PowerStartBlock
MStart.PFacStartBlock
MStart.FrqStartBlock
MStart.ExBlo TripCmd-I
MStart.RemStartBlock-I
MStart.EmgOvr-I
MStart.INSQ-I
MStart.ZSS-I
MStart.STPC Blo-I
50P[1].Active
50P[1].ExBlo
50P[1].Rvs Blo
50P[1].Blo TripCmd
50P[1].ExBlo TripCmd
50P[1].Pickup IA
50P[1].Pickup IB
50P[1].Pickup IC
Description
Signal: JAM Start Delay. JAM(Instantaneous Overcurrent) elements are blocked for the time programmed
under this parameter
Signal: Motor start block current unbalance signal
Generic Start Delay. This value can be used to block any protective element.1
Generic Start Delay. This value can be used to block any protective element.2
Generic Start Delay. This value can be used to block any protective element.3
Generic Start Delay. This value can be used to block any protective element.4
Generic Start Delay. This value can be used to block any protective element.5
Signal: Current transition signal
Signal: Time transition signal
Signal: Motor stop block other protection functions
Signal: System IA RotaryFieldDetection Normal
Signal: System IA RotaryFieldDetection Reverse
Signal: Motor start block voltage unbalance signal.
Signal: Undervoltage Start Delay. Undervoltage elements are blocked for the time programmed under this
parameter
Signal: Overvoltage Start Delay. Overvoltage elements are blocked for the time programmed under this
parameter
Signal: Power Start Delay. Power elements are blocked for the time programmed under this parameter
Signal: Power Factor Start Delay. Power Factor elements are blocked for the time programmed under this
parameter
Signal: Frequency Start Delay. Frequency elements are blocked for the time programmed under this
parameter
Module Input State: External Blocking of the Trip Command
State of the module input: Remote Motor Start Blocking
State of the module input: Emergency Override. Signal has to be active in order to release the thermal
capacity of the motor. Please notice that by doing this you run the risk of damaging the motor. "EMGOVR" has
to be set to "DI" or "DI or UI" for this input to take effect
State of the module input: INcomplete SeQuence
State of the module input: Zero Speed Switch
State of the module input: With this setting a Digital Input keeps the Motor in the RUN mode, even when the
motor current drops below STPC (motor stop current).
Signal: Active
Signal: External Blocking
Signal: Reverse Blocking
Signal: Trip Command blocked
Signal: External Blocking of the Trip Command
Signal: Pickup IA
Signal: Pickup IB
Signal: Pickup IC
www.eaton.com
EMR-4000
IM02602009E
897