Setting Group Parameters of the External Protection Module
Parameter
Description
Function
Permanent activation or deactivation of module/element. Inactive,
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Blo TripCmd
Permanent blocking of the Trip Command of the
module/element.
ExBlo TripCmd Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo TripCmd Fc=active".
EMR-4000
Setting range
Active
Inactive,
Active
Inactive,
Active
Inactive,
Active
www.eaton.com
IM02602009E
Default
Menu path
Inactive
[Protection Para
/<1..4>
/ExP
/ExP[1]]
Inactive
[Protection Para
/<1..4>
/ExP
/ExP[1]]
Inactive
[Protection Para
/<1..4>
/ExP
/ExP[1]]
Inactive
[Protection Para
/<1..4>
/ExP
/ExP[1]]