Eaton EMR-4000 Installation, Operation And Maintenance Manual page 708

Motor relay
Table of Contents

Advertisement

Parameter
Description
WD 4 Trip Function Winding 4 Trip Function
WD 4 Alarm
Winding 4 Threshold for Temperature Alarm
Only available if: Device Planning: Alarm Function = Use
WD 4 t-Delay
Winding 4 If this time is expired a Temperature Alarm will
be generated.
Only available if: Device Planning: Alarm Function = Use
WD 4 Trip
Winding 4 Threshold for Temperature Trip
Only available if: Device Planning: Trip Function = Use
WD 5 Alarm
Winding 5 Alarm Function
Function
WD 5 Trip Function Winding 5 Trip Function
WD 5 Alarm
Winding 5 Threshold for Temperature Alarm
Only available if: Device Planning: Alarm Function = Use
EMR-4000
Setting range
Inactive,
Active
0 - 200°C
0 - 360min
0 - 200°C
Inactive,
Active
Inactive,
Active
0 - 200°C
www.eaton.com
IM02602009E
Default
Menu path
Active
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 4]
80°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 4]
1min
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 4]
100°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 4]
Active
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 5]
Active
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 5]
80°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 5]
708

Advertisement

Table of Contents
loading

Table of Contents