Setting Group Parameters of the Aux. Overvoltage Module
Parameter
Description
Function
Permanent activation or deactivation of module/element. Inactive,
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Blo TripCmd
Permanent blocking of the Trip Command of the
module/element.
ExBlo TripCmd Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo TripCmd Fc=active".
Pickup
Vn refers to the rated secondary voltage of the aux VT.
Only available if: Device Planning: 59.Mode = V>
t
Tripping delay
EMR-4000
Setting range
Active
Inactive,
Active
Inactive,
Active
Inactive,
Active
0.01 - 1.30Vn
0.00 - 300.00s
www.eaton.com
IM02602009E
Default
Menu path
Inactive
[Protection Para
/<1..4>
/Aux-V-Prot
/59A[1]]
Inactive
[Protection Para
/<1..4>
/Aux-V-Prot
/59A[1]]
59A[1]: Inactive
[Protection Para
59A[2]: Active
/<1..4>
/Aux-V-Prot
/59A[1]]
Inactive
[Protection Para
/<1..4>
/Aux-V-Prot
/59A[1]]
59A[1]: 1.2Vn
[Protection Para
59A[2]: 1.1Vn
/<1..4>
/Aux-V-Prot
/59A[1]]
0.00s
[Protection Para
/<1..4>
/Aux-V-Prot
/59A[1]]
609