Current and Ground Current Measurement

Phase and Ground
Current Inputs:
Nominal Currents:
Max. Measuring Range:
Capacity:
Overcurrent Proof:
Power Consumption:
Sensitive Ground Current
Inputs:
Nominal Currents:
Max. Measuring Range:
Capacity:
Overcurrent Proof:
Power Consumption:
Frequency Range:
Terminals:
Plug-in Connector with Integrated Short-Circuiter
(Conventional Current Inputs)
1 A / 5 A
Up to 40 x In (phase currents)
Up to 25 x In (ground current standard)
4 x In/continuously
30 x In / 10 s
100 x In / 1 s
250 x In / 10 ms (1 half-wave)
Phase current inputs
At In = 1 A
S = 25 mVA
At In = 5 A
S = 90 mVA
Ground current input
At In = 1 A
S = 25 mVA
At In = 5 A
S = 90 mVA
1 A / 5 A with 50:0.025 core balance CT
Up to 2.5 x In
2 x In/continuously
10 x In / 10 s
25 x In / 1 s
100 x In / 10 ms (1 half-wave)
At 1 A
S = 550 mVA
At 0.1 A
S = 7 mVA
At 5 A
S = 870 mVA
At 0.5 A
S = 10 mVA
50 Hz / 60 Hz ±10%
Screw-type terminals with integrated short-circuiters (contacts)
EMR-4000
www.eaton.com
IM02602009E