Eaton EMR-4000 Installation, Operation And Maintenance Manual page 515

Motor relay
Table of Contents

Advertisement

Device Planning Parameters of the 51P Module
Parameter
Description
Mode
Mode
Definition of Vn:
Vn is dependent on the »Measuring Channel« setting in the current protection modules.
In case that this parameter is set to "Phase to Phase":
Vn=MainVT sec
In case that this parameter is set to "Phase to Neutral":
Main VT sec
Vn=
3
If the parameter »VT con« within the field parameters is set to »Phase to Phase« the
setting »Phase to Neutral« in the current modules is effectless.
EMR-4000
Options
51P[1]: Non-directional
51P[2]: Do not use,
Non-directional
51P[3]: Do not use,
Non-directional
www.eaton.com
Default
Menu path
Non-directional
[Device Planning]
IM02602009E
515

Advertisement

Table of Contents
loading

Table of Contents