Parameter
Description
Trip
Signal: Zone Interlocking Trip
Fault Type
Fault Type
Zone Interlocking Output Logic [X2]
The following current protective function elements serve as the Phase Zone Interlock OUTPUT start functions:
51P[1];
50P[1]; and
50P[2].
The following current protective function serves as the Ground Zone Interlock OUTPUT start functions:
51X[1];
50X[1];
50X[2];
51R[1];
50R[1] and
50R[2].
EMR-4000
Setting range
Inactive,
Active
Phase,
Ground,
Both
www.eaton.com
IM02602009E
Default
Menu path
Active
[Protection Para
/<1..4>
/ZI
/Zone Trip]
Both
[Protection Para
/<1..4>
/ZI
/Zone Trip]