Eaton EMR-4000 Installation, Operation And Maintenance Manual page 469

Motor relay
Table of Contents

Advertisement

Parameter
Description
ZSS
Zero Speed Switch
EmgOvr
Emergency override options. Signal has to be active in
order to release the thermal capacity of the motor. Please
notice that by doing this you run the risk of damaging the
motor. "EMGOVR" has to be set to "DI" or "DI or UI" for
this input to take effect.
RemStartBlock
Remote Motor Start Blocking
Only available if: RemStartBlo Fc = Active
EmgOvr
Emergency Override. Signal has to be active in order to
release the thermal capacity of the motor. Please notice
that by doing this you run the risk of damaging the motor.
"EMGOVR" has to be set to "DI" or "DI or UI" for this input
to take effect
INSQ
INcomplete SeQuence
Only available if: INSQReportFrom = Active
ZSS
Zero Speed Switch
Only available if: ZSS = Active
STPC Blo
With this setting a Digital Input keeps the Motor in the
RUN mode, even when the motor current drops below
STPC (motor stop current).
t-Blo-IOC
Phase Instantaneous Overcurrent Start Delay. 50P[x]
elements are blocked for the time programmed under this
parameter, while the motor is starting.
EMR-4000
Setting range
Inactive,
Active
Inactive,
DI,
UI,
DI or UI
1..n, Dig Inputs
1..n, Dig Inputs
1..n, Dig Inputs
1..n, Dig Inputs
1..n, Dig Inputs
0.03 - 1.00s
www.eaton.com
IM02602009E
Default
Menu path
Inactive
[Protection Para
/Global Prot Para
/MStart
/Start Control]
Inactive
[Protection Para
/Global Prot Para
/MStart
/Start Control]
-.-
[Protection Para
/Global Prot Para
/MStart
/Motor Inputs]
-.-
[Protection Para
/Global Prot Para
/MStart
/Motor Inputs]
-.-
[Protection Para
/Global Prot Para
/MStart
/Motor Inputs]
-.-
[Protection Para
/Global Prot Para
/MStart
/Motor Inputs]
-.-
[Protection Para
/Global Prot Para
/MStart
/Motor Inputs]
0.05s
[Protection Para
/Global Prot Para
/MStart
/Start Delay Timer]