Parameter
Description
Count2
Open Counts Allowed #2
Only available if:Bwear Curve Fc = Active
Current3
Interrupted Current Level #3
Only available if:Bwear Curve Fc = Active
Count3
Open Counts Allowed #3
Only available if:Bwear Curve Fc = Active
Current4
Interrupted Current Level #4
Only available if:Bwear Curve Fc = Active
Count4
Open Counts Allowed #4
Only available if:Bwear Curve Fc = Active
Current5
Interrupted Current Level #5
Only available if:Bwear Curve Fc = Active
Count5
Open Counts Allowed #5
Only available if:Bwear Curve Fc = Active
Current6
Interrupted Current Level #6
Only available if:Bwear Curve Fc = Active
Count6
Open Counts Allowed #6
Only available if:Bwear Curve Fc = Active
Current7
Interrupted Current Level #7
Only available if:Bwear Curve Fc = Active
Count7
Open Counts Allowed #7
Only available if:Bwear Curve Fc = Active
EMR-4000
Setting range
1 - 32000
0.00 - 2000.00kA
1 - 32000
0.00 - 2000.00kA
1 - 32000
0.00 - 2000.00kA
1 - 32000
0.00 - 2000.00kA
1 - 32000
0.00 - 2000.00kA
1 - 32000
www.eaton.com
IM02602009E
Default
Menu path
10000
[Control
/Bkr
/Bwear]
1.15kA
[Control
/Bkr
/Bwear]
10000
[Control
/Bkr
/Bwear]
3.00kA
[Control
/Bkr
/Bwear]
1900
[Control
/Bkr
/Bwear]
5.00kA
[Control
/Bkr
/Bwear]
850
[Control
/Bkr
/Bwear]
6.00kA
[Control
/Bkr
/Bwear]
500
[Control
/Bkr
/Bwear]
13.00kA
[Control
/Bkr
/Bwear]
110
[Control
/Bkr
/Bwear]
433