APPENDIX C
C.5IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP
The D30 can be configured for IEC 61850 via the EnerVista UR Setup software as follows.
1.
An ICD file is generated for the D30 by the EnerVista UR Setup software that describe the capabilities of the IED.
2.
The ICD file is then imported into a system configurator along with other ICD files for other IEDs (from GE or other ven-
dors) for system configuration.
3.
The result is saved to a SCD file, which is then imported back to EnerVista UR Setup to create one or more settings
file(s). The settings file(s) can then be used to update the relay(s) with the new configuration information.
The configuration process is illustrated below.
Creating ICD (GE Multilin)
IED (UR-series)
OR
EnerVista
Setting files
UR Setup
(.URS)
System
specification data
System specification tool
Updating IED with new configuration (GE Multilin)
EnerVista UR Setup
URS 1
URS 2
Write settings file
Write settings
to other devices
file to device
UR relay 1
UR relay 2
The following acronyms and abbreviations are used in the procedures describing the IED configuration process for IEC
61850:
BDA: Basic Data Attribute, that is not structured
DAI: Instantiated Data Attribute
DO: Data Object type or instance, depending on the context
GE Multilin
C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP
IEC 61850 related
Process of
configuration for the
creating ICD
IED (GSSE/GOOSE,
(vendor 2)
server, logical node
prefixes, MMXU
deadbands, GGIO2
control, etc.)
ICD file 2
ICD file 1
SSD file
Vendor specific tool
for updating new
configuration to IED
URS X
(vendor 2)
Vendor relay 2
UR relay X
Figure 0–1: IED CONFIGURATION PROCESS
D30 Line Distance Protection System
Process of
creating ICD
(vendor 3)
ICD file 3
Import
System configurator
System Configuration
(network, cross-
communications, IED setting
modification, etc.)
SCD file
Vendor specific tool
for updating new
configuration to IED
(vendor 3)
Vendor relay 3
Ethernet

C.5.1 OVERVIEW

C
Process of
creating ICD
(vendor ) N
ICD file N
Vendor specific tool
for updating new
configuration to IED
(vendor ) N
Vendor relay N
842790A1.CDR
C-11

Advertisement

Table of Contents
loading

Table of Contents