Ul Standards - YASKAWA CIMR-AC2B0004 Quick Start Manual

Table of Contents

Advertisement

10 UL Standards

10
UL Standards
UL Standards Compliance
The UL/cUL mark applies to products in the United States and Canada. It indicates that UL has performed product
testing and evaluation, and determined that their stringent standards for product safety have been met. For a product to
receive UL certification, all components inside that product must also receive UL certification.
This drive is tested in accordance with UL standard UL508C and complies with UL requirements. The conditions
described below must be met to maintain compliance when using this drive in combination with other equipment:
Installation Area
Do not install the drive to an area greater than pollution degree 2 (UL standard).
Main Circuit Terminal Wiring
YASKAWA recommends using closed-loop crimp terminals on all drive models. UL/cUL approval requires the use of
closed-loop crimp terminals when wiring the drive main circuit terminals on models CIMR-AC2B0110 to 2B0415 and
4B0058 to 4B0414. Use only the tools recommended by the terminal manufacturer for crimping.
The wire gauges listed in the tables below are YASKAWA recommendations. Refer to local codes for proper wire gauge
selections.
Note: The mark
indicates the terminals for protective ground connection. (as defined in IEC60417-5019)
Grounding impedance;
200 V: 100 Ω or less
400 V: 10 Ω or less
Model
CIMR-
Terminal
AC
R/L1, S/L2, T/L3
U/T1, V/T2, W/
2B0004
T3
2B0006
–, +1, +2
2B0010
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/
T3
2B0012
–, +1, +2
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/
T3
2B0021
–, +1, +2
B1, B2
EN 40
For Europe and
China
<1>
Recommen
Applicable
ded Gauge
Gauge
mm
2
mm
2
2.5
2.5 to 6
2.5
2.5 to 6
2.5 to 6
2.5 to 6
2.5
2.5 to 6
2.5
2.5 to 6
2.5
2.5 to 6
2.5 to 6
2.5 to 6
2.5
2.5 to 6
4
2.5 to 6
2.5
2.5 to 6
4 to 6
2.5 to 6
4
4 to 6
UL/cUL Mark
For U.S.A
<2>
Recommen
Applicable
ded Gauge
Gauge
AWG, kcmil
AWG, kcmil
14
14 to 10
14
14 to 10
14 to 10
14 to 10
10
14 to 10
12
14 to 10
14
14 to 10
14 to 10
14 to 10
10
14 to 10
10
12 to 10
10
12 to 10
12 to 10
14 to 10
10
12 to 10
YASKAWA ELECTRIC TOEP C710606 48A - AC Drive A1000 1000Hz Software - Quick Start Guide
For Asia
<3>
Recommen
Applicable
ded Gauge
Gauge
mm
2
mm
2
2
2 to 5.5
2
2 to 5.5
2
2 to 5.5
2
2 to 5.5
2
2 to 5.5
2
2 to 5.5
2
2 to 5.5
2
2 to 5.5
2
2 to 5.5
3.5
2 to 5.5
5.5
3.5 to 5.5
3.5
3.5 to 5.5
5.5
3.5 to 5.5
2
2 to 5.5
3.5
3.5 to 5.5
Tightening
Screw
Torque
Size
N m (lb.in.)
1.2 to 1.5
M4
(10.6 to 13.3)
1.2 to 1.5
M4
(10.6 to 13.3)
1.2 to 1.5
M4
(10.6 to 13.3)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents