Low Voltage Wiring for Control Circuit Terminals
Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local codes for wiring. Use a class
2 power supply for the control circuit terminal when not using the internal control power supply of the drive. Refer to
NEC Article 725 Class 1, Class 2, and Class 3 Remote-Control, Signaling, and Power Limited Circuits for requirements
concerning class 1 circuit conductors and class 2 power supplies.
Input / Output
Open Collector Outputs
Digital inputs
Analog inputs / outputs
Drive Short-Circuit Rating
This drive is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical amperes, 600
Vac maximum (Up to 240 V in 200 V class drives , up to 480 V for 400 V class drives) when protected by Bussmann
Type FWH fuses as specified in
Drive Motor Overload Protection
Set parameter E2-01 (motor rated current) to the appropriate value to enable motor overload protection. The internal
motor overload protection is UL listed and in accordance with the NEC and CEC.
E2-01 Motor Rated Current
Setting Range: Model Dependent
YASKAWA ELECTRIC TOEP C710606 48A - AC Drive A1000 1000Hz Software - Quick Start Guide
Model
FWH-400A
FWH-400A
FWH-600A
FWH-700A
FWH-800A
FWH-1000A
Three-Phase 400 V Class
FWH-40B
FWH-50B
FWH-70B
FWH-70B
FWH-90B
FWH-90B
FWH-80B
FWH-100B
FWH-125B
FWH-200B
FWH-250A
FWH-250A
FWH-250A
FWH-250A
FWH-250A
FWH-350A
FWH-400A
FWH-500A
FWH-600A
FWH-700A
FWH-800A
FWH-800A
Terminal Signal
DM+, DM-
S1-S8, SN, SC, SP, HC, H1, H2
+V, -V, A1, A2, A3, AC, AM, FM
Input Fuse Installation on page
Fuse Type
Manufacturer: Bussmann
Fuse Ampere Rating (A)
Power Supply Specifications
Requires class 2 power supply.
Use the internal LVLC power supply of the drive. Use class 2 for external power supply.
Use the internal LVLC power supply of the drive. Use class 2 for external power supply.
46.
10 UL Standards
400
400
600
700
800
1000
40
50
70
70
90
90
80
100
125
200
250
250
250
250
250
350
400
500
600
700
800
800