Digital Operator
Parameters were set outside the allowable setting range.
oPE02
A contradictory setting is assigned to multi-function contact
inputs H1-01 through to H1-08.
• The same function is assigned to two inputs. (this excludes
"External fault" and "Not used")
oPE03
• Input functions which require the setting of other input
functions were set alone.
• Input functions that are not allowed to be used
simultaneously have been set.
• The run command source (b1-02) or frequency reference
source (b1-01) is set to 3 but no option card is installed.
oPE05
• The frequency reference source is set to pulse input but
H6-01 is not 0.
Settings to multi-function analog inputs H3-02 and H3-10
and PID functions conflict.
• H3-02 and H3-10 are set to the same value. (this excludes
oPE07
settings 0 and F)
• PID functions have been assigned to both analog inputs and
the pulse input at the same time.
A function has been set that cannot be used in the control
oPE08
mode selected.(might appear after control mode change)
The V/f pattern setting is incorrect.
oPE10
Auto-Tuning Errors
Digital Operator
Motor data fault
The input motor data are not valid. (e.g. the base frequency
Er-01
and base speed do not fit).
Minor Fault
Er-02
• The wiring is faulty.
The STOP button was pressed and Auto-Tuning was
Er-03
canceled.
Resistance fault
• Wrong input data.
Er-04
• Auto tuning exceeded the given time frame.
• Calculated values out of range.
No-Load Current Error
• Incorrect data was entered.
Er-05
• Auto tuning took too long.
• Calculated values out of range.
Rated Slip Error
• Wrong data input.
Er-08
• Auto tuning exceeded the given time frame.
• Calculated values out of range.
Current detection error
• One or all output phases are lost.
Er-12
• Current is either too low or exceeds the drives rating.
• The current sensors are faulty.
Excessive V/f Setting
• The torque reference exceeded 20% during Auto-Tuning.
End1
• The calculated no-load current is above 80% of the motor
rated current.
Rated current alarm
End3
Adjusted Slip Calculation Error
End4
The slip that was calculated is outside the allowable range.
Resistance Tuning Error
The resistance value that was calculated is outside the
End5
allowable range.
YASKAWA ELECTRIC TOEP C710606 48A - AC Drive A1000 1000Hz Software - Quick Start Guide
Cause
Cause
Corrective Action
Set parameters to the proper values.
• Fix any incorrect settings.
• Refer to the Technical Manual for more details.
• Install the required option card.
• Correct the values set to b1-01 and b1-02.
• Fix any incorrect setting.
• Refer to the Technical Manual for more details.
• Fix any incorrect setting.
• Refer to the Technical Manual for more details.
• Check the V/f pattern settings.
• Refer to the Technical Manual for more details.
Corrective Action
Re-enter the data and repeat Auto-Tuning.
• Check the wiring.
Repeat the Auto-Tuning.
• Check the input data.
• Check the wiring.
• Re-enter the data and repeat the Auto-Tuning.
• Check the wiring.
• Make sure, that the drive rating fits to the motor.
• Check the load. (Auto-Tuning should have been performed
without the load connected.)
• Replace the drive.
• Check the V/f pattern setting.
• Perform Auto-Tuning without the load connected.
• Check the input data and repeat Auto-Tuning.
Check the input data and repeat tuning.
• Make sure the data entered for Auto-Tuning is correct.
• Double check the data that was entered for the Auto-Tuning
process.
• Check the motor and motor cable connection for faults.
8 Troubleshooting