7 Parameter Table
No.
Name
Maximum
These parameters are only applicable when
E1-04
Output
E1-03 is set to F.
Frequency
To set linear V/f characteristics, set the
same values for E1-07 and E1-09. In this
Maximum
E1-05
case, the setting for E1-08 will be
Voltage
disregarded. Ensure that the four
Base
E1-06
frequencies are set according to these rules:
Frequency
E1-09 ≤ E1-07 < E1-06 ≤ Ε1−11 ≤ E1-04
Middle Output
E1-07
Frequency
Middle Output
E1-08
Frequency
Voltage
Minimum
E1-09
Output
Frequency
Minimum
Output
E1-10
Note: Some parameters may not be
Frequency
available depending on the control mode.
Voltage
• E1-07, E1-08 and E-10 are available only
E1-13
Base Voltage
• E1-11, E1-12 and E-13 are available only
Motor 1 Parameters
Motor Rated
Sets the motor nameplate full load current in
E2-01
Current
Amps.
Motor Rated
E2-02
Sets the motor rated slip.
Slip
Motor
E2-03
No-Load
Sets the no-load current for the motor.
Current
Number of
E2-04
Sets the number of motor poles.
Motor Poles
Motor
Sets the phase-to-phase motor resistance.
E2-05
Line-to-Line
Automatically set during Auto-Tuning.
Resistance
Sets the voltage drop due to motor leakage
Motor Leakage
E2-06
inductance as a percentage of motor rated
Inductance
voltage.
Multi-Function Digital Inputs
Multi-Function
Digital Input
H1-01 to
Terminal S1 to
Selects the function of terminals S1 to S8.
H1-08
S8 Function
Selection
Note: Major functions are listed at the end of the table.
Multi-Function Digital Outputs
Terminal M1-
Set the function for the relay output M1-
H2-01
M2 function
M2.
selection
Terminal M3-
Sets the function for the relay output M3-
H2-02
M4 function
M4.
selection
Terminal M5-
Sets the function for the relay output M5-
H2-03
M6 function
M6.
selection
EN 30
Description
Output Voltage (V)
E1-05
E1-12
E1-13
E1-08
E1-10
E1-09
E1-07 E1-06 E1-11 E1-04
Frequency (Hz)
in V/f Control.
in V/f Control.
No.
Name
Watt Hour
H2-06
Output Unit
Selection
Note: Major functions are listed at the end of the table.
Multi-Function Analog Inputs
Terminal A1
H3-01
Signal Level
Selection
Terminal A1
H3-02
Function
Selection
Terminal A1
H3-03
Gain Setting
Terminal A1
H3-04
Bias Setting
Terminal A3
H3-05
Signal Level
Selection
Terminal A3
H3-06
Function
Selection
Terminal A3
H3-07
Gain Setting
Terminal A3
H3-08
Bias Setting
Terminal A2
H3-09
Signal Level
Selection
Terminal A2
H3-10
Function
Selection
Terminal A2
H3-11
Gain Setting
Terminal A2
H3-12
Bias Setting
Analog Input
H3-13
Filter Time
Constant
Analog Input
Terminal
H3-14
Enable
Selection
YASKAWA ELECTRIC TOEP C710606 48A - AC Drive A1000 1000Hz Software - Quick Start Guide
Description
Outputs a 200 ms pulse signal when the
watt-hour counter increases by the units
selected.
0: 0.1 kWh units
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units
0: 0 to 10 V
1: –10 to 10 V
Sets the function of terminal A1.
Sets the level of the input value selected in
H3-02 when 10 V is input at terminal A1.
Sets the level of the input value selected in
H3-02 when 0 V is input at terminal A1.
0: 0 to 10 V
1: –10 to 10 V
Sets the function of terminal A3.
Sets the level of the input value selected in
H3-06 when 10 V is input at terminal A3.
Sets the level of the input value selected in
H3-06 when 0 V is input at terminal A3.
0: 0 to 10 V
1: –10 to 10 V
2: 4 to 20 mA
3: 0 to 20 mA
Note: Use DIP switch S1 to set input
terminal A2 for a current or a voltage input
signal.
Sets the function of terminal A2.
Sets the level of the input value selected in
H3-10 when 10 V (20 mA) is input at
terminal A2.
Sets the level of the input value selected in
H3-10 when 0 V (0 or 4 mA) is input at
terminal A2.
Sets a primary delay filter time constant for
terminals A1, A2, and A3. Used for noise
filtering.
Determines which of the analog input
terminals will be enabled when a digital
input programmed for "Analog input
enable" (H1-
= C) is activated.
1: Terminal A1 only
2: Terminal A2 only
3: Terminals A1 and A2 only
4: Terminal A3 only
5: Terminals A1 and A3
6: Terminals A2 and A3
7: All terminals enabled