6 Start Up
Auto-Tuning (T1-
Auto-Tuning automatically sets up the motor data relevant drive parameters.
Type
Stationary Auto-Tuning for
Line-to-Line Resistance
Do not touch the motor until the Auto-Tuning is finished.
Failure to comply may result in minor or moderate injury. Voltage is still applied to the motor during the tuning
process, even thought the motor may not be rotating.
For Auto-Tuning enter the Auto-Tuning menu and perform the steps shown in the figure below. The number of name
plate data to be entered depends on the selected type of Auto-Tuning. This example shows Terminal Resistance Auto-
Tuning in V/f control.
Drive mode
display
- MODE -
DRV
Rdy
FREF (OPR)
U1-01= 0.00Hz
U1-02= 0.00Hz
LSEQ
U1-03= 0.00A
LREF
JOG
FWD/REV
FWD
- A.TUNE -
PRG
Mtr Rated Power
T1-02= X.XXkW
(0.00 ~ 650.00)
"X.XXkW"
ESC
DATA
FWD
Set up all name
If Auto-Tuning can not be performed for some reason (no-load operation impossible etc.), then set up the maximum
frequency and voltage in the E1-
NOTICE: The Safe Disable inputs must be closed during Auto-Tuning.
External Reference Selection and Acceleration/ Deceleration Times
Frequency Reference Selection (b1-01)
Set parameter b1-01 according to the frequency reference used.
b1-01
Reference source
0
Operator keypad
1
Analog input
2
Serial Comm.
3
Option Card
4
Pulse input
EN 26
)
Setting
• The drive is used in V/f Control and other Auto-Tuning selections not possible.
• Drive and motor capacities differ.
T1-01 = 2
• Tunes the drive after the cable between the drive and motor has been replaced with a
Enter the
Auto-Tuning Mode
- MODE -
PRG
Auto-Tuning
AUTO
HELP
DATA
FWD
- A.TUNE -
PRG
Rated Current
T1-04= x.xxA
(0.xx ~ x.xxA)
"x.xxA"
ESC
DATA
FWD
plate data
parameters and enter the motor data manually into the E2-
Set the frequency references in the d1-
different reference values.
Apply the frequency reference signal to terminal A1, A2, or A3.
Serial Communications using the RS422/485 port
Communications option card
Set the frequency reference at terminal RP using a pulse train signal.
Application Conditions and Benefits
cable over 50 m long. Assumes Auto-Tuning has already been performed.
CAUTION
- A.TUNE -
PRG
Tuning Mode Sel
T1-01= 2
∗2∗
Term Resistance
ESC
DATA
FWD
- A.TUNE -
DRV
Auto-Tuning
0.00 Hz/ 0.00A
Tuning Ready ?
Press RUN key
ESC
FWD
RUN
The tuning start
display appears
Frequency reference input
YASKAWA ELECTRIC TOEP C710606 48A - AC Drive A1000 1000Hz Software - Quick Start Guide
Select the tuning
method
- A.TUNE -
PRG
Tuning Mode Sel
T1-01=
2
∗2∗
Term Resistance
Entry Accepted
"2"
FWD
- A.TUNE -
DRV
Tune Proceeding
X.XX Hz/ X.XXA
FWD
During the tuning the
After successful tuning
display flashes
"End" is displayed
parameters and use digital inputs to switch over between
- MODE -
DRV
End
Tune Successful
RESET
FWD
parameters.