YASKAWA CIMR-AC2B0004 Quick Start Manual page 31

Table of Contents

Advertisement

No.
Name
Multi-Function Analog Inputs
Multi-Function
Selects the data to be output through multi-
Analog Output
function analog output terminal FM.
H4-01
Terminal FM
Set the desired monitor parameter to the
Monitor
digits available in U -
Selection
enter "103" for U1-03.
Multi-Function
Sets the signal level at terminal FM that is
Analog Output
H4-02
equal to 100% of the selected monitor
Terminal FM
value.
Gain
Multi-Function
Analog Output
Sets the signal level at terminal FM that is
H4-03
Terminal FM
equal to 0% of the selected monitor value.
Bias
Multi-Function
Selects the data to be output through multi-
Analog Output
function analog output terminal AM.
H4-04
Terminal AM
Set the desired monitor parameter to the
Monitor
digits available in U -
Selection
enter "103" for U1-03.
Multi-Function
Analog Output
Sets the signal level at terminal AM that is
H4-05
Terminal AM
equal to 0% of the selected monitor value.
Gain
Multi-Function
Analog Output
Sets the bias value added to the terminal
H4-06
Terminal AM
AM output signal.
Bias
Multi-Function
Analog Output
0: 0 to 10 V
H4-07
Terminal FM
1: -10 to 10 V
Signal Level
2: 4 to 20 mA
Selection
Multi-Function
Analog Output
0: 0 to 10 V
H4-08
Terminal AM
1: -10 to 10 V
Signal Level
2: 4 to 20 mA
Selection
Pulse Input Setting (Freq.)
Sets the terminal RP input signal frequency
Pulse Train
H6-02
that is equal to 100% of the value selected
Input Scaling
in H6-01.
Sets the level of the value selected in H6-01
Pulse Train
H6-03
when a frequency with the value set in H6-
Input Gain
02 is input.
Pulse Train
Sets the level of the value selected in H6-01
H6-04
Input Bias
when 0 Hz is input.
Pulse Output Setting
Select the pulse train monitor output
Pulse Train
function (value of the
H6-06
Monitor
U -
Selection
Example: To select U5-01, set 501.
Sets the terminal MP output signal
Pulse Train
frequency when the monitor value is 100%.
H6-07
Monitor
To have the pulse train monitor output equal
Scaling
the output frequency, set H6-06 to 102 and
H6-07 to 0.
YASKAWA ELECTRIC TOEP C710606 48A - AC Drive A1000 1000Hz Software - Quick Start Guide
Description
. For example,
. For example,
-
part of
).
No.
Name
Motor Protection
0: Disabled
1: General purpose motor (standard fan
cooled)
2: Drive dedicated motor with a speed range
of 1:10
Motor
3: Vector motor with a speed range of 1:100
Overload
4: PM motor with variable torque
L1-01
Protection
5: PM motor with constant torque control
Selection
6: General purpose motor (50 Hz)
The drive may not be able to provide
protection when multiple motors are used,
even if overload protection is enabled in L1-
01. Set L1-01 to 0 and install separate
thermal relay to each motor.
Motor
Overload
Sets the motor thermal overload protection
L1-02
Protection
(oL1) time.
Time
Stall Prevention
0: Disabled.
1: General purpose. Acceleration is
Stall
paused as long as the current is above the
Prevention
L3-02 setting.
L3-01
Selection
2: Intelligent. Accelerate in the shortest
during
possible time without exceeding the L3-02
Acceleration
level.
Note: Setting 2 is not available when using
OLV/PM.
Stall
Prevention
Used when L3-01 = 1 or 2. 100% is equal to
L3-02
Level during
the drive rated current.
Acceleration
0: Disabled. Deceleration at the active
deceleration rate. An ov fault may occur.
1: General purpose. Deceleration is
Stall
paused when the DC bus voltage exceeds
Prevention
the Stall Prevention level.
L3-04
Selection
2: Intelligent. Decelerate as fast as possible
during
while avoiding ov faults.
Deceleration
3: Stall Prevention with braking resistor.
Stall Prevention during deceleration is
enabled in coordination with dynamic
braking.
0: Disabled. Drive runs at a set frequency. A
heavy load may cause speed loss.
Stall
1: Decel time 1. Uses the deceleration
Prevention
time set to C1-02 while Stall Prevention is
L3-05
Selection
performed.
during Run
2: Decel time 2. Uses the deceleration time
set to C1-04 while Stall Prevention is
performed.
Stall
Prevention
Enabled when L3-05 is set to 1 or 2. 100%
L3-06
Level during
is equal to the drive rated current.
Run
Induction Motor Auto-Tuning
Auto-Tuning
2: Stationary Auto-Tuning for Line-to-Line
T1-01
Mode
Resistance
Selection
Motor Rated
Sets the motor rated power as specified on
T1-02
Power
the motor nameplate.
7 Parameter Table
Description
EN 31