Warnings and Alarms
Number
Text
2326
The power card configuration is determined to be
incorrect after the delay for power cards to
register.
2327
Too many power card locations have been
registered as present.
2330
The power size information between the power
cards does not match.
2561
No communication from DSP to ATACD.
2562
No communication from ATACD to DSP (state
running).
2816
Stack overflow control board module
2817
Scheduler slow tasks
2818
Fast tasks
2819
Parameter thread
2820
LCP stack overflow
2821
Serial port overflow
2822
USB port overflow
2836
cfListMempool is too small.
3072–5122 The parameter value is outside its limits.
8
8
5123
Option in slot A: Hardware incompatible with the
control board hardware.
5124
Option in slot B: Hardware incompatible with the
control board hardware.
5125
Option in slot C0: Hardware incompatible with the
control board hardware.
5126
Option in slot C1: Hardware incompatible with the
control board hardware.
5376–6231 Out of memory
Table 8.4 Internal Fault, Code Numbers
ALARM 39, Heat sink sensor
No feedback from the heat sink temperature sensor.
The signal from the IGBT thermal sensor is not available on
the power card. The problem could be on the power card,
on the gate drive card, or the ribbon cable between the
power card and gate drive card.
WARNING 40, Overload of digital output terminal 27
Check the load connected to terminal 27 or remove the
short-circuit connection. Check 5-00 Digital I/O Mode and
5-01 Terminal 27 Mode.
WARNING 41, Overload of digital output terminal 29
Check the load connected to terminal 29 or remove the
short-circuit connection. Check 5-00 Digital I/O Mode and
parameter 5-02 Terminal 29 Mode.
WARNING 42, Overload of digital output on X30/6 or
overload of digital output on X30/7
For X30/6, check the load connected to X30/6 or remove
the short-circuit connection. Check 5-32 Term X30/6 Digi
Out (MCB 101).
For X30/7, check the load connected to X30/7 or remove
the short-circuit connection. Check 5-33 Term X30/7 Digi
Out (MCB 101).
114
Operating Instructions
ALARM 46, Power card supply
The supply on the power card is out of range.
There are 3 power supplies generated by the switch mode
power supply (SMPS) on the power card: 24 V, 5 V, and±18
V. When powered with 24 V DC with the MCB 107 option,
only the 24 V and 5 V supplies are monitored. When
powered with 3-phase mains voltage, all 3 supplies are
monitored.
WARNING 47, 24 V supply low
The 24 V DC is measured on the control card. This alarm
arises when the detected voltage of terminal 12 is <18 V.
Troubleshooting
WARNING 48, 1.8 V supply low
The 1.8 V DC supply used on the control card is outside of
the allowable limits. The power supply is measured on the
control card. Check for a defective control card. If an
option card is present, check for overvoltage.
WARNING 49, Speed limit
When the speed is outside of the specified range in
parameter 4-11 Motor Speed Low Limit [RPM] and
parameter 4-13 Motor Speed High Limit [RPM], the frequency
converter shows a warning. When the speed is below the
specified limit in 1-86 Trip Speed Low [RPM] (except when
starting or stopping), the frequency converter trips.
ALARM 50, AMA calibration failed
Contact the Danfoss supplier or Danfoss Service.
ALARM 51, AMA check U
The settings for motor voltage, motor current and motor
power are wrong. Check the settings in parameters 1-20 to
1-25.
ALARM 52, AMA low I
The motor current is too low. Check the settings.
ALARM 53, AMA motor too big
The motor is too big for the AMA to operate.
ALARM 54, AMA motor too small
The motor is too small for the AMA to operate.
ALARM 55, AMA parameter out of range
The parameter values of the motor are outside of the
acceptable range. AMA cannot run.
ALARM 56, AMA interrupted by user
The user has interrupted the AMA.
ALARM 57, AMA internal fault
Continue to restart the AMA, until the AMA is carried out.
NOTICE
Repeated runs may heat the motor to a level where the
resistance R
however, this behaviour is not critical.
ALARM 58, AMA Internal fault
Contact your Danfoss supplier.
Danfoss A/S © Rev. 06/2014 All rights reserved.
Check for a defective control card.