Using the Service Menu

The Service menu allows users to configure several service related
options, such as when and how to activate service alarms. Service alarms
are used to signal when a sensor needs to be replaced or calibrated.
This menu contains two options: Set Act and Set Time.
The Set Act menu lets users select the action that will be taken. Available
options are: Fault, OFF or Visual
Fault:
A service alarm will be activated whenever there is a fault
status
OFF:
No service alarm will be triggered at any time (factory default
setting)
Visual:
Only a visual service alarm will be activated
The Set Time menu lets users configure a specific deadline at which a
service alarm will be activated.
Use the arrows to scroll between 12 to 24 months to trigger a service
alarm after the specified number of months in service. Select the Reset
option to turn off the Service alarm for a period of 100 days (after the
alarm was triggered).
301EM User Manual
Programming and Calibration
Using the Service Menu