Remote Calibration Steps - Honeywell IAQPoint2 User Manual

Air quality monitor
Hide thumbs Also See for IAQPoint2:
Table of Contents

Advertisement

Available languages

Available languages

Use and Calibration
Remote Calibration on Modbus Network

Remote Calibration Steps

1. On the first line, scroll to the device address and press Enter
2. Scroll through the devices to display the desired device* and press
Enter to select.
3. The second line displays the device's status
4. Scroll to select the desired function, Set Zero to set the device's zero
5. Upon selecting Set Zero, the controller requests confirmation.
6. Press Enter to confirm or Esc to cancel. If confirmed, the controller
sets the 901T's zero. This takes only a few moments and returns to
the default calibration screen.
34
Calib
007
Calibrate Zero?
Set Zero
Set Span
246
901T User Manual
901T
PPM