Conversion Enable/Disable Setting (Un\G0); Ch Time/Count/Moving Average/Time Constant Setting (Un\G1 To 4) - Mitsubishi q64rd User Manual

Rtd input module channel isolated rtd input module
Hide thumbs Also See for q64rd:
Table of Contents

Advertisement

3 SPECIFICATIONS

3.4.3 Conversion enable/disable setting (Un\G0)

3.4.4 CH
time/count/moving average/time constant setting (Un\G1 to 4)
3 - 23
(1) You can make setting to enable/disable temperature conversion on each channel.
(2) Specifying unused channels as "conversion disabled" prevents unnecessary
disconnection detection and also reduces sampling time.
(3) At power-on or reset, the conversion enable/disable setting is set to 000F
channels disabled).
b15 b14 b13 b12 b11 b10
0
0
0
0
[Example]
b15 b14 b13 b12 b11 b10
0
0
0
0
Channels 1 and 2 are conversion enabled.
(4) The Operating condition setting request (Y9) must be turned on/off to make the
conversion enable/disable setting valid.
(1) For each channel for which Averaging processing specification (buffer memory
address 9: Un\G9) and Extended averaging processing specification (buffer
memory address 134: Un\G134) is made, set the averaging time, averaging count,
the number for moving average or time constant for primary delay filter.
(2) Allowable setting range is as follows:
Processing method
Time averaging
Count averaging
Moving average
Primary delay filter
Setting any value outside the above range will result in an error and the operation
will be performed under the previous setting.
(3) This setting will be invalid if sampling is specified for Averaging processing
specification (buffer memory address 9: Un\G9) or Extended averaging
processing specification (buffer memory address 134: Un\G134).
(4) At power-on or reset, this is preset to 0000H. Change the setting according to the
processing method.
(5) The Operating Condition Setting Request (Y9) must be turned on/off to make this
setting valid.
(6) Refer to Section 3.4.5 and 3.4.21 for further details.
b9
b8
b7
0
0
0
0
0
b9
b8
b7
0
0
0
0
0
MELSEC-Q
b6
b5
b4
b3
b2
0
0
0
CH4 CH3 CH2 CH1
0: Conversion enabled
1: Conversion disabled
b6
b5
b4
b3
b2
0
0
0
1
1
Set value
160 to 5000 (ms)
4 to 62500 (times)
4 to 60 (times)
40 to 5000 (ms)
(all
H
b1
b0
b1
b0
0
0
3 - 23