D/A Conversion Enable/Disable (Buffer Memory Address 0: Un\G0); Ch Digital Values (Buffer Memory Addresses 1 To 8: Un\G1 To Un\G8) - Mitsubishi Q62DA User Manual

Logic, melsec-1 series
Hide thumbs Also See for Q62DA:
Table of Contents

Advertisement

3 SPECIFICATIONS

3.4.2 D/A conversion enable/disable (buffer memory address 0: Un\G0)

Un\G0
3.4.3 CH
digital values (buffer memory addresses 1 to 8: Un\G1 to Un\G8)
Output range setting
0: 0 to 20 mA
1: 4 to 20 mA
2: 1 to 5 V
3: 0 to 5 V
4: –10 to 10 V
F: User range setting
3 - 18
(1) Set whether D/A conversion is enabled or disabled for each channel.
(2) It is necessary to set the operating condition setting request (Y9) to ON/OFF to
validate the D/A conversion enable/disable setting. (See Section 3.3.2.)
(3) By default, all channels are set to D/A conversion disabled.
(4) When Q62DA is used, b2 to b7 (CH3 to CH8) become invalid.
b15 b14 b13 b12 b11 b10
0
0
0
0
0
For Q62DA, information for b4 to b15 is fixed at 0.
For Q64DA, information for b4 to b15 is fixed at 0.
(1) This area is used to write digital values for performing D/A conversion from the
PLC CPU as 16-bit signed binary code.
(2) Settings for digital values to be D/A converted when a value outside the valid
digital value setting range is used are listed in Table 3.7.
When a value outside the valid range is written, a check code is stored in the set
value check codes (Un\G11 to Un\G18).
(3) For Q62DA, Un\G3 to Un\G8 (CH3 to CH8) become invalid.
For Q64DA, Un\G5 to Un\G8 (CH5 to CH8) become invalid.
Table 3.7 Output range settings and valid range
Normal resolution mode
Valid range
(practical range)
0 to 4095
(Practical range:
0 to 4000)
–4096 to 4095
(Practical range:
–4000 to 4000)
b9
b8
b7
b6
CH
CH
0
0
0
8
7
Digital value that is set
when a value outside
the valid range is
written
4096 or larger: 4095
–1 or smaller: 0
4096 or larger: 4095
–4097 or smaller: –
4096
b5
b4
b3
b2
b1
CH
CH
CH
CH
CH
6
5
4
3
1: D/A conversion disabled
0: D/A conversion enabled
High resolution mode
Digital value that is set
Valid range
when a value outside
(practical range)
the valid range is
0 to 12287
12288 or larger: 12287
(Practical range:
–1 or smaller: 0
0 to 12000)
-16384 to 16383
16384 or larger: 16383
(Practical range:
–16385 or smaller:
-16000 to 16000)
-12288 to 12287
12288 or larger: 12287
(Practical range:
–12289 or smaller:
-12000 to 12000)
MELSEC-Q
b0
CH
2
1
written
16384
–12288
3 - 18