8 TROUBLESHOOTING

8 TROUBLESHOOTING
This chapter explains the natures of errors which may occur during use of the
Q64RD/Q64RD-G and troubleshooting.

8.1 Error Code List

If an error occurs when data are written to or read from the programmable controller
CPU, the Q64RD/Q64RD-G writes the corresponding error code to the buffer memory
address 19 (Un\G19).
Error Code
(Decimal)
The measurement range setting is other than 0 to 5.8 in the
10
intelligent function module switch setting.
indicates the channel number set incorrectly.
111
A module error at start-up.
Value set in the intelligent function module switch setting 5 is
112
other than 0.
The offset/gain setting is other than 0 and 1 in the intelligent
12
function module switch setting.
indicates the channel number set incorrectly.
The three-/four-wire type setting is other than 0 and 1 in the
13
intelligent function module switch setting.
indicates the channel number set incorrectly.
The G(P).OGSTOR instruction was executed in the
1
161
offset/gain setting mode.
• The G(P).OGSTOR instruction was executed consecutively.
162
• At the time of offset/gain setting, a set value was written to
2
the E
PROM 26 or more times.
• The G(P).OGSTOR instruction was executed for the model
that differs from the model for which the G(P).OGLOAD
163
instruction had been executed.
• The G(P).OGSTOR instruction had been executed before
the G(P).OGLOAD instruction was executed.
The time averaging setting is outside the setting range.
20
indicates the channel number set incorrectly.
The count averaging setting is outside the setting range.
30
indicates the channel number set incorrectly.
The moving average setting is outside the setting range.
31
indicates the channel number set incorrectly.
The time constant setting is outside the setting range.
32
indicates the channel number set incorrectly.
In the offset/gain setting, or when the user setting is restored,
40
Gain value - Offset value
indicates the channel number set incorrectly.
When the offset setting request (Y1, Y3, Y5, Y7) or gain
setting request (Y2, Y4, Y6, Y8) is turned on in the offset/gain
50
setting mode, the offset/gain setting of the intelligent function
module switch setting on that channel is not user-set.
indicates the channel number set incorrectly.
When the offset setting request (Y1, Y3, Y5, Y7) or gain
setting request (Y2, Y4, Y6, Y8) is turned on in the offset/gain
51
setting mode, the "offset value" or "gain value" of that channel
is outside the measurement range.
indicates the channel number set incorrectly.
The offset setting request and gain setting request were
52
turned on simultaneously in the offset/gain setting mode.
indicates the channel number set incorrectly.
1: This error code is written into G(P).OGSTOR instruction's completion status area (S) +1, not into the buffer memory address 19 (Un\G19).
8 - 1
Description
0.1 [C].
Remedy
Make a correct setting in the intelligent function module
switch setting. (Refer to Section 4.5.)
Switch power off, then on again. If the error recurs, the
module may have failed. Consult your local Mitsubishi service
center or representative.
Set a correct value in the intelligent function module switch
setting. (Refer to Section 4.5.)
Make a correct setting in the intelligent function module
switch setting. (Refer to Section 4.5.)
Make a correct setting in the intelligent function module
switch setting. (Refer to Section 4.5.)
Do not execute the G(P).OGSTOR instruction in the
offset/gain setting mode.
• Execute the G(P).OGSTOR instruction only once for one
module.
• At the time of offset/gain setting, write a set value only once
at one time.
Execute the G(P).OGLOAD and G(P).OGSTOR instructions
for the same model.
Set a correct value at the buffer memory address 1 to 4
(Un\G1 to 4). (Refer to Section 3.4.4).
Set a correct value at the buffer memory address 1 to 4
(Un\G1 to 4). (Refer to Section 3.4.4).
Set a correct value at the buffer memory address 1 to 4
(Un\G1 to 4). (Refer to Section 3.4.5.)
Set a correct value at the buffer memory address 1 to 4
(Un\G1 to 4). (Refer to Section 3.4.5.)
Set a correct value in the buffer memory, or measure and
check the resistance of the RTD input terminals.
Make a correct setting in the intelligent function module
switch setting. (Refer to Section 4.5.)
Check the measurement range and set the offset/gain value
within the range. (Refer to Section 3.1.1 (Q64RD) or 3.1.2
(Q64RD-G).)
Reexamine the sequence program so that they do not turn on
simultaneously.