7 ONLINE MODULE CHANGE

7.3 Online Module Change Procedure

7.3.1 When factory default is used and initial setting was made with GX Configurator-TI

7 - 4
There are the following online module change procedures depending on whether the
user range setting has been made or not, whether the initial setting of GX Configurator-
AD has been made or not, and whether the other system exists or not.
Range setting
Factory default
Factory default
User range setting
User range setting
User range setting
User range setting
(1) Conversion disable
(a)
Set Conversion enable/disable setting (buffer memory address 0: Un\G0)
for all channel conversion disable and turn the operating condition setting
request (Y9) from OFF to ON to stop conversion.
After confirming that conversion has stopped with the Conversion
Completion Flag (buffer memory address 10: Un\G10), turn off Operating
Condition Setting Request (Y9).
Initial setting
GX Configurator-TI
Sequence program
GX Configurator-TI
GX Configurator-TI
Sequence program
Sequence program
MELSEC-Q
Other system
Reference section
Section 7.3.1
Section 7.3.2
Present
Section 7.3.3
Absent
Section 7.3.4
Present
Section 7.3.5
Absent
Section 7.3.6