3 SPECIFICATIONS
Device No.
Signal Name
Conversion
XE
Completion Flag
XF
Error Flag
3 - 13
(1) This signal (XE) turns on when the temperature conversion values of all conversion-enabled
channels are stored into buffer memory after power-on or hardware reset.
(2) When averaging processing is performed, this signal also turns on when the temperature
conversion values are stored into buffer memory after completion of averaging processing.
(3) This signal (XE) varies as described below depending on whether the Operating Condition
Setting Completion Signal (X9) has turned on or off.
• When the Operating Condition Setting Completion Signal (X9) has turned on
(stop
conversion)
1) Temperature conversions of the enabled channels are started.
2) After the temperature conversion values are stored into buffer memory, the conversion
completion flags (buffer memory address 10: Un\G10) are turned on.
3) This signal (XE) is turned on after the temperature conversion values of all conversion-
enabled channels enabled for conversion are stored into buffer memory.
• When the Operating Condition Setting Completion Signal (X9) has turned off
(conversion
stop)
1) The conversion completion flags (buffer memory address 10: Un\G10) of all channels are
turned off.
2) This signal (XE) is turned off.
Note that if conversion is stopped, the temperature conversion values stored in buffer
memory are held at the data immediately before the stop.
(4) This signal (XE) does not turn on when all channels are disabled for conversion.
(1) This signal (XF) turns on when an error occurs.
(2) To clear the error code, turn on the Error Clear Request (YF).
Error Flag (XF)
Error Clear Request (YF)
Description
Error code is read during this period.
MELSEC-Q
3 - 13