Status; Modem Connection Status - ABB SREA-01 User Manual

Ethernet adapter module
Hide thumbs Also See for SREA-01:
Table of Contents

Advertisement

55

Status

This page shows some status information about the Modbus interface that is used
for drive connection. The status screen is split into multiple columns and rows.
Transparent Modbus/TCP indicates the Modbus traffic from Modbus/TCP to Modbus
RTU, this functionality is also know as Modbus gateway. Information about
connected devices is indicated with device-specific counters. Clear all counters by
pressing 'clear' button below the Serial Modbus Status window. The Modbus/TCP
messages field shows information about requests that originate from a Modbus/TCP
master attached to SREA-01 and that are redirected by the internal Modbus/TCP
gateway to the drive interface. Other Modbus messages field shows information
about requests that originate from SREA-01, either from internal applications such
as Logging and Alarms, or web pages such as the parameter page.
The values displayed in the Serial Modbus Status display:
Valid Responses - Counts valid responses from the drives.
Serial Timeouts - The number of time-outs from attached drives.
Exceptions - Counts all exception responses from the connected drives.
CRC Errors - The number of checksum errors on incoming Modbus/RTU
responses.
Buffer Overruns - If an incoming Modbus/RTU response is larger than 300 bytes,
this will cause the input buffer to overflow.
Frame Errors - If an incoming Modbus/RTU response has incorrect length or some
other fault in the frame, this will cause a Frame Error.

Modem connection status

Modem connection status indicates the modem status. The values displayed:
User interface

Advertisement

Table of Contents
loading

Table of Contents