4.4.6
FX
-4AD-TC
2N
Specifications
Number of input points
Input signal
Rated temperature range
Digital output
Resolution
Overall accuracy
Time required for
conversion
Input characteristics
Insulation method
Number of I/O points
occupied
A-50
PLC User's Manual - Analog Control Edition
3UC
Centigrade (°C)
• Type K: -100°C to +1200°C
• Type J: -100°C to +600°C
• Type K: -1000 to +12000
• Type J: -1000 to +6000
• Type K: 0.4°C
• Type J: 0.3°C
+12000
(Type K)
+6000
(Type J)
-100°C
0
+600°C
(Type J)
-1000
• The photocoupler is used to insulate the analog input area from the PLC.
• The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other.
8 points (Taken from either the input or output points of the PLC.)
FX
-4AD-TC
2N
4ch
Thermocouple type K or J
JIS C 1602-1995
• Type K: -148°F to +2192°F
• Type J: -148 ° F to +1112°F
• Type K: -1480 to +21920
• Type J: -1480 to +11120
• Type K: 0.72°F
• Type J: 0.54°F
± (0.5% for full scale +1°C)
(240ms±2%) × number of selected channels
+1200°C
(Type K)
Temperature
4 Comparison of Performance Specifications
4.4 Temperature Sensor Input
Fahrenheit (°F)
+21920
(Type K)
+11120
(Type J)
-148
F
°
0
+1112
F
+2192
°
(Type J)
(Type K)
-1480
Temperature
F
°