1. Analog input
Specifications
Number of input points
Analog input range
Absolute maximum input
Offset
Gain
Digital input/output
Resolution
Ambient temperature:
25±5°C
Ambient temperature:
0±55°C
Time required for
conversion
I/O characteristics
2. Analog output
Specifications
Number of output points
A-42
PLC User's Manual - Analog Control Edition
3UC
-100mV to +100mV DC
(Input resistance: 200 kΩ)
• -10V to +10V DC:
-32V to +5V DC
• -100mV to +100mV DC:
-320mV to +50mV DC
• -10V to +10V DC:
-5V to +32V, and Gain - Offset > 1V
• -100mV to +100mV DC:
-50mV to +320mV, and Gain - Offset > 10mA
• -10V to +10V DC:
With sign, 16 bits, binary
• -100mV to +100mV DC:
With sign, 12 bits, binary
312.5μV (20V × 1/64000)
50μV (200mV × 1/4000)
• -10V to +10V DC:
±0.3% (±60mV) for 20V full scale
• -100mV to +100mV DC:
±0.5% (±1mV) for 200mV full scale
• -10V to +10V DC:
±0.5% (±100mV) for 20V full scale
• -100mV to +100mV DC:
±1.0% (±2mV) for 200mV full scale
When the input mode is set to "0":
+32767
+32000
-10V
FX
Voltage input
-10V to +10V DC
±15V
1ms × number of selected channels
0
+10V
-32000
-32768
FX
Voltage output
4 Comparison of Performance Specifications
4.3 Mixed Analog Input/Output
-5A
2N
Current input
4ch
-20mA to +20mA DC
4mA to 20mA DC
(Input resistance: 250 Ω)
±30mA
-32mA to +10mA
-10mA to +32mA, and
Gain - Offset > 1 mA
With sign, 15 bits, binary
1.25μA (40mA × 1/32000)
10μA (40mA × 1/4000)
±0.3% (±120μA) for 40mA full scale
Same accuracy for 4mA to 20mA input
±0.5% (±200μA) for 40mA full scale
Same accuracy for 4mA to 20mA input
When the input mode is set to "2":
+32767
+32000
-20mA
0
-32000
-32768
When the input mode is set to "1":
+32767
+32000
2mA
0
4mA
-4000
-5A
2N
Current output
1ch
+20mA
20mA