Details Of Table Output Error - Mitsubishi Electric FX3G User Manual

Hide thumbs Also See for FX3G:
Table of Contents

Advertisement

FX
/FX
/FX
/FX
/FX
3S
3G
3GC
3U
FX
-4DA (4-channel Analog Output)
3U
6.5

Details of table output error

When an error related to the table output function occurs, the error code is stored in BFM#90, and the device
number or the buffer memory that has developed the error is stored in BFM#91.
1. Error code table and details of error source numbers
Error code
(BFM#90)
K111
K121
K122
K131
K132
K151
K152
K161
K162
K171
K172
K21
K22
K23
K31
K32
K33
E-50
PLC User's Manual - Analog Control Edition
3UC
Details of error
The number of patterns in the data table that is held in
the PLC does not meet the following requirement.
1 ≤ Number of patterns ≤ 10
The number of points in the data table that is held in the
PLC does not meet the following requirement.
1 ≤ Number of patterns ≤ 99
The number of points in the data table that is held in the
buffer memory does not meet the following requirement.
1 ≤ Number of points ≤ 99
"The condition after output at final point in pattern"
specified in the data table that is held in the PLC is not 0
or 1.
"The condition after output at final point in pattern"
specified in the data table that is held in the buffer
memory is not 0 or 1.
The output update time in the data table that is held in the
PLC does not meet the following requirement.
1 ≤ Output update time ≤ 32767
The output update time in the data table that is held in the
buffer memory does not meet the following requirement.
1 ≤ Output update time ≤ 32767
The output update time unit in the data table that is held
in the PLC is not 0, 1, 2 or 3.
The output update time unit in the data table that is held
in the buffer memory is not 0, 1, 2 or 3.
The interpolation method in the data table that is held in
the PLC is not 0, 1 or 2.
The interpolation method in the data table that is held in
the buffer memory is not 0, 1 or 2.
The head device number BFM#98 in the data table to be
transferred is out of the setting range.
The value indicated by b0 to b3 of the transfer command
BFM#99 is not 0 or 1.
The value indicated by b4 to b7 of the source register
type in BFM#99 is not 0 or 1.
Any of the output patterns BFM#81 to #84 does not meet
the following requirement.
1 ≤ Output pattern ≤ 10
The number of table outputs in BFM#85 to #88 does not
meet the following requirement.
0 ≤ Number of repetitions of output ≤ 32767
The bit corresponding to each channel in the table output
start/stop command in BFM#80 is not 0 or 1.
6 Table Output Function
6.5 Details of table output error
Table output error source number
(BFM#91)
Device number where the number of
patterns is specified (same as the head
device number in the data table)
Device number where the number of
patterns is specified
Number of BFM where the number of
points is specified
Device number where "the condition after
the final point output point in pattern" is
specified
Number of BFM where "the condition after
output point in the pattern" is specified
Device number where the output update
time is specified
Number of BFM where the output update
time is specified
Device number where the output update
time unit is specified
Number of BFM where the output update
time unit is specified
Device number where the interpolation
method is specified
Number of BFM where the interpolation
method is specified
K98
K99
K99
One of K81 to K84
One of K85 to K88
K80

Hide quick links: