Fx 2N -4Ad-Pt - Mitsubishi Electric FX3G User Manual

Hide thumbs Also See for FX3G:
Table of Contents

Advertisement

FX
/FX
/FX
/FX
/FX
3S
3G
3GC
3U
3UC
Common Items
4.4.5
FX
-4AD-PT
2N
Specifications
Number of input points
Input signal
Input signal current
Rated temperature range
Digital output
Resolution
Overall accuracy
Time required for
conversion
Input characteristics
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method
• The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other.
Number of I/O points
8 points (Count either the input or output points of the PLC.)
occupied
PLC User's Manual - Analog Control Edition
Centigrade (°C)
3-wire platinum resistance thermometer sensor(s)
-100°C to +600°C
-1000 to +6000
0.2°C to 0.3°C
+6000
-100°C
0
+600°C
Temperature
-1000
4 Comparison of Performance Specifications
FX
-4AD-PT
2N
4ch
DIN43760
Pt100 JIS C 1604-1997
JPt100 JIS C 1604-1981
1mA(Constant current system)
±1.0% for full scale
60ms (15ms × 4ch)
+11120
-148
4.4 Temperature Sensor Input
Fahrenheit (°F)
-148 ° F to +1112 ° F
-1480 to +11120
0.36°F to 0.54°F
°
F
0
°
+1112
F
Temperature
-1480
A-49
A
B
C
D
E
F
G
H
I
J

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fx3sFx3gcFx3uFx3uc

Table of Contents