Create a sequence program.
To change the output characteristics, write the offset data (BFM#10 to #13) and the gain data
(BFM#14 to #17) in the sequence program, and then turn on the corresponding bit of BFM#9 for
the corresponding channel.
Example: Program for changing the output characteristics of channels 1 and 2 (For FX
PLCs):
X000
M0
T0
FNC224
LD=
7
Transfer the sequence program to change the output characteristics.
Transfer the sequence program, and start the PLC.
After the PLC is started and the output characteristic write command (X000) is turned on, the offset
data and gain data will be written.
Since the offset data and gain data are stored in the EEPROM incorporated in FX
sible to delete the pre-written sequence program.
8
Check the analog output signals
Check that the output analog signals correspond to the set output data.
PLC User's Manual - Analog Control Edition
FNC 12
MOV
FNC 12
MOV
FNC 16
FMOV
P
FNC 16
FMOV
P
FNC 12
MOV
FNC 12
K0
U0\G9
MOV
→ If analog signals are not correctly output, refer to Chapter 9 "Troubleshooting."
7 Changing Output Characteristics
Cancellation of setting change
K3030
U0\G19
prohibition mode
P
Output mode specification for
HFF00
U0\G0
channels 1 to 4
P
SET
M0
K50
T0
Setting of offset data (channels 1 and 2)
K1000
U0\G10
K2
K3000
U0\G14
K2
Setting of gain data (channels 1 and 2)
Offset/gain setting value write command
H0003
U0\G9
P
Setting change prohibition
K0
U0\G19
P
7.1 Procedure for Changing Output Characteristics