Changing Output Characteristics - Mitsubishi Electric FX3G User Manual

Hide thumbs Also See for FX3G:
Table of Contents

Advertisement

FX
/FX
/FX
/FX
/FX
3S
3G
3GC
3U
3UC
FX
-4DA (4-channel Analog Output)
3U
7.

Changing Output Characteristics

For FX
-4DA, the standard output characteristics are provided for each output mode (BFM#0)at the time of
3U
factory shipment.
Changing the offset data (BFM#10 to #13) and gain data (BFM#14 to #17) can change the output
characteristics of each channel. This chapter describes how to change the output characteristics.
7.1
Procedure for Changing Output Characteristics
1
Cancel the setting change prohibition mode.
If setting change is prohibited, write K3030 in BFM#19. The setting change prohibition mode will be
canceled.
2
Determine the output mode (BFM#0).
Determine the output mode (BFM#0) optimum for the selected channels and the voltage/current
specifications.
Set value (HEX)
0
1
2
3
4
5 to E
F
Example: Enter "HFF00" in BFM to set output mode 0 for channels 1 and 2 and prevent use chan-
nels 3 and 4
Cautions regarding data setting
• If a value "1" or "4" is set for a channel, the output characteristics of the channel cannot be changed.
• Set the optimum output mode for the analog signal to be output.
PLC User's Manual - Analog Control Edition
Output mode
Voltage output mode
Voltage output analog value mV
specification mode
Current output mode
Current output mode
Current output analog value μA
specification mode
Setting not allowed
Channel not used
7 Changing Output Characteristics
7.1 Procedure for Changing Output Characteristics
Analog output range
-10 V to +10 V
The characteristic cannot be changed.
0 mA to 20 mA
4 mA to 20 mA
The characteristic cannot be changed.
-
-
Digital input range
-32000 to +32000
0 to 32000
0 to 32000
-
-
E-53
A
B
C
D
E
F
G
H
I
J

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fx3sFx3gcFx3uFx3uc

Table of Contents