Analog Output; Fx 3U -4Da-Adp - Mitsubishi Electric FX3G User Manual

Hide thumbs Also See for FX3G:
Table of Contents

Advertisement

FX
/FX
/FX
/FX
/FX
3S
3G
3GC
3U
3UC
Common Items
4.2

Analog Output

4.2.1
FX
-4DA-ADP
3U
Specifications
Number of output points
Analog output range
Offset
Gain
Digital input
Resolution
Ambient temperature:
25±5°C
Ambient temperature:
0 to 55°C
If the external load resistance (Rs) is less than
5 kΩ, the accuracy increases as shown in the
following formula: (Increase: 100 mV per 1%)
Reference
• FX
Time required for D/A
conversion
• FX
Output characteristics
• The photocoupler is used to insulate the analog output area from the PLC.
Insulation method
• The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other.
Number of I/O points
0 point (This number is not related to the maximum I/O points of the PLC.)
occupied
PLC User's Manual - Analog Control Edition
Voltage output
0V to 10V DC
(External load: 5 k to 1 MΩ)
Impossible to change
2.5mV (10V × 1/4000)
±0.5% (±50mV) for 10V full scale
±1.0% (±100mV) for 10V full scale
47100
-0.9 %
Rs+47
for 10 V full scale
/FX
Series PLC : 200μs (Data updated every scan time.)
3U
3UC
/FX
/FX
Series PLC : 250μs (Data updated every scan time.)
3S
3G
3GC
10V
4000
0
Digital input
4 Comparison of Performance Specifications
FX
-4DA-ADP
3U
Current output
4ch
4mA to 20mA DC
(External load: 500 Ω or less)
Impossible to change
12 bits, binary
4μA (16mA × 1/4000)
±0.5% (±80μA) for 16mA full scale
±1.0% (±160μA) for 16mA full scale
20mA
4mA
0
Digital input
4.2 Analog Output
-
4000
A-35
A
B
C
D
E
F
G
H
I