Changing Of Output Characteristics - Mitsubishi Electric FX3G User Manual

Hide thumbs Also See for FX3G:
Table of Contents

Advertisement

FX
/FX
/FX
/FX
/FX
3S
3G
3GC
3U
FX
-1DA-BD (1-channel Analog Output)
3G
5.

Changing of Output Characteristics

The output characteristics can be changed using sequence programs in FX
5.1
Example: Changing of Voltage Output Characteristics
This section describes an example of a program that can change the digital value range from 400 to 2000
(when analog output range is 1 to 5 V) to 0 to 10000.
A specified digital value is inputted into D100.
1. Output characteristics
Voltage output characteristics
(product specifications)
10V
5V
1V
0
400
2. Example of program (For FX
For example, create the following program to change the digital output data (D100) of the board A.
M8001
Normally
OFF
FNC230
D100
LD>=
M10
G-20
PLC User's Manual - Analog Control Edition
3UC
2000
4000
Digital value input
Series PLC)
3G
FNC237
K0
AND<=
FNC 22
MUL
FNC 23
DDIV
FNC 20
ADD
FNC 12
MOV
5.1 Example: Changing of Voltage Output Characteristics
Digital value characteristics
to be changed
Y-axis
2000
(5V)
400
(1V)
0
Desired digital value (D100)
M8260
M8264
D100 K10000
M10
D100
K1600
D101
D101
K10000
D103
D103
K400
D107
D107
D8260
5 Changing of Output Characteristics
/FX
Series PLCs.
3S
3G
X-axis
10000
Sets the output mode of 1st board
to the voltage output mode (0 V to 10 V).
Sets the output mode to the
output holding mode.
Check to make sure the digital
value (D100) is in range.
Calculation for changing output
characteristics.
Stores the operation result in D8260.