Error Status - Mitsubishi Electric FX3G User Manual

Hide thumbs Also See for FX3G:
Table of Contents

Advertisement

FX
/FX
/FX
/FX
/FX
3S
3G
3GC
3U
3UC
FX
-4AD-TC-ADP (4-channel Thermocouple Data Input)
3U
4.7

Error Status

If an error is detected on TC-ADP, the error status data will be stored in the corresponding special data
register.
The following table shows the special data registers that store the error status data:
• FX
Series PLC
3S
Special data register
D8288
• FX
/FX
Series PLC
3G
3GC
Special data register
1st
D8288
• FX
/FX
Series PLC
3U
3UC
1st
D8268
Check the ON/OFF status of each bit of the error status data register to determine the error. Errors are
assigned to the bits as shown in the following table. Create a program to detect errors.
Bit
The temperature measurement data
b0
of channel 1 is outside the specified
range, or disconnection is detected.
The temperature measurement data
b1
of channel 2 is outside the specified
range, or disconnection is detected.
The temperature measurement data
b2
of channel 3 is outside the specified
range, or disconnection is detected.
The temperature measurement data
b3
of channel 4 is outside the specified
range, or disconnection is detected.
b4
EEPROM error
1. Caution regarding use of error status data
If a TC-ADP hardware error (b6) or TC-ADP communication data error (b7) is once detected, it is necessary
to clear the error status with a program at next power-on of the PLC.
For this reason, be sure to create the following program:
• For FX
/FX
3S
3G
M8000
Normally
ON
M8002
Initial pulse
*1.
"1st" for the FX
PLC User's Manual - Analog Control Edition
Stores the error status data.
2nd
D8298
Stores the error status data.
Special data register
2nd
3rd
D8278
D8288
D8298
Description
/FX
/FX
/FX
Series PLC
3GC
3U
3UC
FNC 12
D8288
MOV
RST
RST
FNC 12
K4M0
MOV
/FX
/FX
PLC.
3S
3G
3GC
Description
Description
4th
Stores the error status data.
Bit
b5
Averaging time setting error
b6
TC-ADP hardware error
b7
TC-ADP communication data error
b8 to b15
Unused
-
K4M0
Error status in the 3rd
M6
b6 = OFF (TC-ADP hardware error)
Error status in the 3rd
M7
b7 = OFF (TC-ADP communication data error)
D8288
4 Programming
4.7 Error Status
Description
Description
-
*1
analog special adapter
*1
analog special adapter
K
L
M
L-25